28
NEVER USE AN OPEN FLAME FOR LEAK TESTING.
TO TEST VALVE PRESSURES (INPUT RATES):
The pressure taps are located on the front side of the valve (see Figure 38).
1. Using a long flat bladed screwdriver, turn set screw one (1) turn counter-clockwise to loosen.
2. Place
5
/
16
in (8 mm) I.D. hose over the pressure taps.
3. Check pressures using a manometer.
4. When finished, remove hose and tighten set screw.
Initial Installation
QUALIFIED INSTALLERS ONLY
Figure 38: Valve Details.
See Dexen User Manual for E33ID valve details
Always check for
gas leaks with a soap and water solution after completing the required
pressure test.
29
Pilot
Adjustment
Screw
Manifold Pressure
Tap
Inlet
Pressure
Tap
Servo
Regulator
Pilot
Solenoid
Burner
Solenoid
Gas IN
a
Djusting
t
he
p
iLot
f
Lame
(
Does
not
appLy
to
e33iD
moDeLs
):
Figure 39:
Proper Pilot Flame.
.375-.500
(10-13mm)
Flame Sensor
The pilot flow adjustment is set to maximum at the
factory and should not need to be adjusted. The pilot
flame should envelope ⅜” to ½” (10 to 13mm) of
the Flame sensor (see Figure 39). However, should
the need arise, follow Steps 1- 2 below.
1. The adjustment screw can be reached through
the front of the unit using a 10 inch long blade
head screw driver (see Figure 38 for location on
valve).
2. Turn the adjustment screw clockwise to decrease
or counterclockwise to increase pilot flame.