Initial Installation
WARNING: Operation of this heater when not connected to a properly installed and maintained
venting system can result in carbon monoxide (CO) poisoning and possible death.
c
LeaRances
to
c
ombustibLes
:
Figure 25: Mantle width and height.
Maintain sufficient clearances for operation, service
and maintenance.
• A minimum distance of 24” (610 mm) is required
from the centerline of the unit to the sidewalls.
• Minimum clearance for any combustible facing is 30”
(762 mm) from the bottom of the unit.
• A 12” (305 mm) wide mantel can be mounted at a
minimum height of 36” (914 mm) from the bottom
of unit.
• If installed at floor level there must be a minimum of
16” (406 mm) of non-combustible material in front
of the unit. Once unit is rasied 2” or more no floor
protection is required.
• Unit can be installed with combustible material
underneath, as long as it is raised 4” off the floor.
• Minimum ceiling clearance is 60” from bottom of
unit.
m
inimum
f
iRepLace
s
ize
:
Table 4: Minimum dimensions of fireplace for E33 to be installed into.
Width At Front
Width At Back
Height
Depth
Fireplace Dimensions
32” (813 mm)
20” (508 mm)
20” (508 mm)
17
1
/
2
” (445 mm)
NOTE: Space must be provided for gas line on left side of unit for servicing purposes. The E33 can only
be installed into masonary or zero-clearance fireplaces.
20
37”
36”
35”
34”
33”
32”
31”
30”
1
2
3
4
5
6
7
8
9
10 11 12
MA
NTL
E H
EIGH
T
(F
ROM UNIT BOT
TO
M)
M A N T L E D E P T H
Minimum Mantle Clearances
12” MANTLE
n
on
-c
ombustibLe
b
uiLD
o
ut
:
The E33I / E33ID may be installed and vented into any solid fuel fireplace that has been installed in
accordance with the National, Provincial/State and local building codes and has been constructed of
noncombustible materials. Before starting, refer to please reference the information in Table 5 and
Figures 27 and 28.
Additionally should extra installation depth be required, the existing fireplace may be re-faced with a
build out in front, constructed completely of non-combustible framing and finishing material (see Figure
26). The build out must be constructed and sealed to prevent any heat from collecting in-between the
existing fireplace and the finishing material. Prior to constructing the build out it is important to know
the overall size of the selected surround panel. For ease of installation and servicing it is recommended
to only have a small overlap from the finished opening. Refer to the minimum fireplace size (table 4)
to compare with the selected surround panel. The flex venting is permitted to have smooth sweeping,
slight angle bends but must not be kinked in any way.
IMPORTANT - Contact your local dealer for further information prior to construction and installation.