4.
Analogue output
Setting and calibrating the analogue output
4.1
Lower limit
Input:
0 … 22 mA
Standard setting: 4 mA
4.2
Upper limit
Input:
0 … 22 mA
Standard setting: 20 mA
4.3
Alarm value
Input:
0 … 22 mA
Value to be output at pending alarm
(Standard setting 2 mA)
4.4
Alarm mode
Selection:
Alarm:
Alarm is output.
Alarm / Freeze
Measurement value drops to 0, or
current measurement value.
Freeze:
Last measurement value
remains pending until fault
rectification at the output signal.
4.5
Analog output 1
Submenu
4.5.1 Calibration 4 mA
Selection:
Key functions can be used to set the
Setting the output current
current and equalise it to the receiver
side.
4.5.2 Calibration 20 mA
Selection:
Key functions can be used to set the
Setting the output current
current and equalise it to the receiver
side.
4.6
Analog output 2
Submenu
4.6.1 Calibration 4 mA
Selection:
Key functions can be used to set the
Setting the output current
current and equalise it to the receiver
side.
4.6.2 Calibration 20 mA
Selection:
Key functions can be used to set the
Setting the output current
current and equalise it to the receiver
side.