5. Electrical connection
Different variants of the Evaluation unit are available for the evaluation of the sensor signals.
The
MSE 300-FH
variants are supplied in an IP65 housing and can be installed in a free environment
according to the specification.
The
MSE 300-DR
variants are designed for installation in an electrical cabinet. The
MSE 300-DR2
is a
variant of the MSE 300-DR and can be extended to a display as required.
Only the standard variants of all Evaluation units are described below. The Evaluation unit can be installed
at a maximum distance of 300 m from the sensor. A cable of type “Ölflex Classic 110 CY” is recommended.
The cable should be four wired, twisted and shielded. A minimum cable cross-section of 0.75 mm
2
should
be observed. For distances more than 150 m the cable cross-section should be adjusted.
5.1 Terminal layout MSE 300-DR
Fig. 15: Electrical connection of the MSE 300-DR
Current output
- 4 ... 20 mA
Current output
+ 4 ... 20 mA
Input Power
supply 0 V DC
Input Power
24 V DC
Not used
Alarm relay
NC (break contact)
Alarm relay
C
Alarm relay
NO (make contact)
1
2
3
4
5
6
7
8
Digital pulse
output (-)
Digital pulse
output (+)
RS 485
Interface Data B
RS 485
Interface Data A
Sensor connection
Cable 4
RS 485 Data B
Sensor connection
Cable 3
RS 485 Data A
Sensor connection
Cable 2
Power supply 0 V
Sensor connection
Cable 1
Power 24 V
9
10
11
12
13
14
15
16