13. Electrical connections
NB: the electrical connections and start-up of the gearmotors are shown in the EL34
control panel installation manual.
i
Before connecting the power supply, make sure the plate data correspond to that of the
mains power supply.
An omnipolar disconnection switch with a contact opening distance of at least 3mm
must be fitted on the mains supply.
Check there is an adequate residual current circuit breaker and overcurrent cutout upstream
of the electrical system.
Use a H05RN-F 3G1.5 type electric cable and connect it to the terminals L (brown), N (blue),
(yellow/green) in the automation.
Secure the cable using a special cable clamp and remove the sheath only where the clamp is.
Connection to the mains power supply (in the section outside the automation) is made on an
independent channel separated from that containing the connections to the control and safety
devices.
The channel must penetrate the automation by at least 50mm via the holes on the base plate.
Make sure there are no sharp edges that may damage the power supply cable.
Make sure the mains power wires (230V) and the accessory wires (24V) are separated.
The cables must be double insulated. Remove their sheaths near the relative connecting ter-
minals, and secure them with cable fasteners (not supplied).