INSTALLATION CONSIDERATIONS,
continued
PLACEMENT AND SPACING
Consult your local distributor to help you plan the most
efficient installation of your fans.
Ensure fan placement is such that the fans blades are a
minimum of 10' from any manned working suface (floor or
mezzanine)
Ensure fan blade does not extend into exclusion zone.
Extensions are available if required. See Fig. 2.
Avoid mounting fans directly under lights or skylights to
avoid visual strobing affect.
NOTE:
If the fan is part of a networked system, ensure placement is
in accordance with the building layout.
NOTE:
Be certain to comply with all local and national codes during
installation.
For fans that will be subjected to high cross winds (open
bay doors, outdoor applications or air conditioning
diffuser ducts) the fan must be at least one fan diameter
(as measured from the end of the winglet) from open
bays or A/C ducts mounted below the blade plane or
there must be at least one fan diameter (as measured
from the end of the winglet) for A/C ducts mounted at or
above the blade plane.
In addition, all outdoor mounted fans must be protected
from exposure from the elements. Consult your local
distributor for outdoor patio applications.