© Entrematic
Group AB 2015
10
6020031A — Commercial HVLS Fans
November 2016
FAN MOUNT (TYPICAL MOUNTING TYPES),
continued
If building support beam is not level, ensure proper fan
clearance using the mounting information shown on
page 6 or add mounting extensions as required to ensure
clearance. See Fig 2.
I-BEAM MOUNTING
1. Locate fan centered square to the bottom flange of the
I-beam.
2. Locate and secure the clamp plates (6017852) using the
provided 3/8-16UNC hex serrated flange nuts and 3/8-
16UNC X 2 1/2" long bolts. See Fig. 3.
NOTE:
Ensure that the clamp plates overlap the I-beam flange by
at least 30%.
3. Torque the nuts to 20-28 ft-lbs.
SOLID BEAM MOUNTING
(6018175 — CONCRETE; 6018026 — WOOD)
1. Locate the beam bracket (6018108). Ensure that the
bottom flange of the bracket is below the bottom of the
beam and square to the beam.
NOTE:
The vertical flange of the beam bracket must be square with
respect to the floor. Shim as required.
2. Using the holes in the beam bracket as a template, mark
and drill at least four (4) 9/16" dia. holes through the beam.
Space the holes as widely as practical. See Fig. 4.
3. Locate both beam brackets with respect to the holes and
fasten using 3/8" dia. grade 5 bolts (not provided). Torque
to 20-28 ft-lbs. Locking hardware (nuts and washers)
required.
Do not use lag bolt style fasteners to secure the solid
beam bracket.
Fig. 3