INPuTS
Command
Function
Description
1 2 N.O Automatic closing
Permanently closing the contact enables automatic closing.
1 3 N.O Opening
With DIP1=ON the closure of the contact activates an opening operation.
Step-by-step
With DIP1=OFF the closure of the contact activates an opening or closing
operation in the following sequence: open-stop-close-open.
Note: if automatic closing is enabled, the stop is not permanent but at a
time that is set by the TC.
1 4 N.O Closing
The closing manoeuvre starts when the contact is closed.
1 6 N.C Reversal safety
device
Opening the safety contact triggers a reversal of the movement (reopening)
during a closing operation.
41 8 N.C Reversal safety
device
Opening the safety contact triggers a reversal of the movement (reopening)
during a closing operation.
1 9 N.C Stop
Opening the safety contact stops the current operation.
1 9 N.O Non-pulse command Permanently opening the safety contact enables the operation by non-
pulse command.
In this state, the opening (1-3/1-20) and closing (1-4) controls function only
if held in the pressed position, and the automation stops when the controls
are released.
All safety switches, the step-by-step control and the automatic closing
function are disabled.
1 20 N.O Partial opening
The closing of the contact activates a partial opening operation of the
duration set with the RP trimmer.
Once the automation stops, the partial opening control performs the
opposite operation to the one performed before stoppage.
0 11 N.C Closure limit switch
The opening of the limit switch contact stops the closure operation.
0 12 N.C Opening limit switch The opening of the limit switch contact stops the opening operation.
0 17 N.O limit switch photocell By-pass photocell
OuTPuTS
Output
Value
Description
1 +
0
–
24 V = / 0,5 A
Accessories power supply.
Power supply output for external accessories, including automation status
lamp.
0 14
24 V = / 50 W
(2 A)
Flashing light (LAMPH).
Activated during opening and closing operations.
400 V~ / 4 A
Three-phase motor.
Note
: if the direction of rotation of the motor is incorrect for the desired direction
of movement, swap the U - W phases.
U W V
M
3 ~
5.1 49E ELECTRONIC CONTROL PANEL - CONNECTIONS
Operation by non-pulse command
Operation by pulse command