NETWORK ANALYZER
MPR-53CS
Technical Data
Operating Voltage (Un)
: Please look behind the device.
Operating Frequency (f)
: 45-65 Hz
Auxiliary supply Power Consumption
: < 4 VA
Measuring Input Power Consumption
: < 1 VA
VIn
: 10-300 V AC 45-65 Hz. (L-N)
: 10-500 V AC 45-65 Hz. (L-L)
I
In
: 0.05 - 5.5 A~
1-120 A~ (for CT-25)
Measuring Range
: 10V...200 kV AC
: 0...215 M (W,VAr,VA)
: 99999999999.9 kWh, kVArh
Class
: 1% ± 1 digit [(10%-110%) xFull Scale]
Voltage Transformer ratio (Vtr)
: 0,1 ... 4000,0
Current Transformer Ratio (Ctr)
: 1 ... 2000
Max. Ctr x Vtr
: 40.000
Hour SP
: 1-9999 hour (programmable)
Demand Time
: 1-60 min. (programmable)
Serial Interface
: MODBUS RTU (RS 485)
Optically Isolated, programmable
Baud Rate
: 2400-38400 bps
Address
: 1-247
Parity
: No, Odd, Even, 8 Data Bits, 2 Stop Bits
Relay Output
: 2 NO, 5 A, 1250 VA
Pulse Output
: NPN Transistör
Switch Period
: Min. 100 msec. pulse period
80 msec. pulse width
Operatimg Current
: Max. 50 mA
Operating Voltage
: 5.....24 V DC, max. 30 VDC
Input
: 12...48 V AC / DC
Ambient Temperature
: -5°C; +50°C
Display
: Red LED Display
Dimensions
: PR-19, PK-26
Equipment Protection Class
: Double Installation-Class II ( )
Box Protection Class
: IP 40 (front panel)
Box Material
Installation
: Panel Mounted (PR-19)
Rail Mounted (PK-26)
Wire Crossection For Terminal Block
: 2.5 mm
2
Weight
: 0.45 kg (PR-19, PK-26)
Installation Class
: Class III
Panel Size
: 91x91 mm (PR-19)
46x107 mm (PK-26)
Factory Settings
Transformer :
Ctr (Current Transformer Ratio) : 0001
trn (Turn number for CT-25): 01
Utr (Voltage Transformer Ratio) : 0001.0
CAL (Calculation Method) : 1
Pin :
0000 (Not Activated)
RS-485 :
Adr (Address) : 1
Bau (Baud Rate) : 9600
PAr (Parity) : no
PRECAUTIONS FOR INSTALLATION AND SAFE USE
In CT-25 (120A) compliant models, only CT-25 current transformer must be used.
Other type of CT’s have a high risk to damage to device.
Failure to follow those instructions will result in death or serious injury.
- Disconnect all power before working on equipment.
- When the device is connected to the network, do not remove the front panel.
- Do not try to clean the device with solvent or the like.Only clean with dry cloth.
- Verify correct terminal connections when wiring.
- Electrical equipment should be serviced only by your component seller.
- Only for rack panel mounting.
- The type of cı̇rcuı̇t breaker must be F and current lı̇mı̇t value must be 1A
- No responsı̇bı̇lı̇ty ı̇s taken on by manufacturer or any its subsidiories for any conditions about the wrong using of this device
No responsibility is assured by the manufacturer or any of its subsidiaries for any consequences
arising out of the use of this material.
Eng Cnt :
E-1 (Energy Counter 1) : on
E-2 (Energy Counter 2) : on
PULSE :
rAt (Ratio) : 1k
o-1 (Output 1) : A-I
o-2 (Output 2) : r-L
dEtı
(Delay Time) : 15
hoU r :
hoU r SP (Setpoint) : 0000
ACt : on
out : 1
PULSE Cnt :
C-1 ACt (Pals Counter 1) : on
C-2 ACt (Pals Counter 2) : on
C-1 rAt ıo (Ratio) : 0001
C-2 rAt ıo (Ratio) : 0001
LAT Ch :
bUt ton : on
ın PUT : oFF
AUT o : oFF
Set point :
SP -01....-16 ACt : oFF
8