Entes MPR-53CS Manual Download Page 3

NETWORK ANALYZER

MPR-53CS 

Pulse Menu 

In this menu, 3 parameter can be selected. “PUL oUt rAt ıo, 

PUL oUt o-1, PUL oUt o-2”.

PUL oUt rAt ıo : 

In this menu, the pulse ratio of pulse outputs is 

1, 10, 100 (Wh/VArh); 1, 10, 100 (kWh/kVArh); 1 MWh/MVArh. 

PUL oUt o-1 / PUL oUt o-2 : 

Pulse is taken for respected consumption 

which assigned in “PUL oUt rAt ıo”. 

o-1/o-2 parameters can be set the below settings; 

ACt (Export/Import), A-I (Active Import), A-E (Active Export),

rEA (Inductive / Capacitive),  r-L (Reactive Inductive), 

r-C (Reactive Capacitive). 
Press SET button for 3 sec. (trA Fo menu is displayed.) 

“PUL SE oUt” menu.

Press SET button “PUL oUt rAt ıo” menu is displayed. 

/PUL oUt o-2” menu. 

Press SET button (1k / A-I / r-L blink)

By using UP/DOWN buttons, select required parameter of value.

Press SET button (Data is entered but is not activated yet. For activating 

the new data please follow the below steps.)

Press ESC button one by one until “SAU E SEt  yES” is displayed.

When “SAU E SEt yES” is displayed, press SET button. If you press 

ESC button or choose “no” option instead of “yES” option by using UP/

DOWN buttons, new data will be cancelled and previous value will be 

activated.

Energy Counter (Eng Cnt) Menu:

MPR-53CS has 2 energy counters: 

Energy Counter 1 (E-1), Energy Counter 2 (E-2).

“E-1 / E-2” have 4 parameters: 

on : “E-1 / E-2” counters count without depending on any parameters.  

ı-1 : It counts when “E-1 / E-2” counter is “on” in digital input 1 (Activate E-1/E-2 

counters, when digital input 1 is on).

ı-2 : It counts when “E-1 / E-2” counter is “on” in digital input 2.

E-2: When “E-2” counter is active, “E-1” counter do not count. (It is only “E-1” 

counters parameter)

E-1: When “E-1” counter is active, “E-2” counter do not count. (It is only “E-2” 

counters parameter)

Note: 

When “E-2” is chosen in “E-1” counter and when “E-1” is chosen in 

parameters, if digital inputs hasn’t got the information “1” both of the counters count 

but if one or both of the counters has got the information, both of the counters don’t 

count.

Press SET button for 3 sec. (trA Fo menu is displayed)

“Eng Cnt” menu.

Press SET button (Eng Cnt E-1 menu is displayed).

Press SET button (on blinks)

By using UP/DOWN buttons, select required parameters.

Press SET button. (Data is entered, but is not activated yet. For 

activating the new data please follow the below steps)
Press ESC button one by one until “SAU E SEt  yES” is displayed.

When “SAU E SEt yES” is displayed, press SET button. If you press 

ESC button or choose “no” option instead of “yES” option by using UP/

DOWN buttons, new data will be cancelled and previous value will be activated.

User Password Setup : 

and activate a 4 digit user password for preventing device setting from 

the illegal usage. 

There are 2 sub menus under “Pın” menu.

Changing of User Password :

This menu is to change the user password. 

Note: 

 Factory default value for user password is 

“0000”.

Press SET button for 3 sec. (trA Fo menu is displayed.)

Press SET button (Pın ACt IUA tE menu is displayed.)

“Pın CHA n9E” menu is displayed.

By using UP/DOWN/SET buttons, enter the old password.

By using UP/DOWN/SET buttons, enter the new password.

By using UP/DOWN/SET buttons, re-enter the new password.

Press SET button, “Pın CHA ngE” is displayed (Data is entered but 

is not activated yet. For activating the new data please follow the 

below steps). 
Press ESC button one by one until “SAU E SEt yES” is displayed. 

When “SAU E SEt yES” is displayed, press SET button. If you 

press ESC button or choose “no” option instead of “yES” option by 

using UP/DOWN buttons, new data will be cancelled and previous 

value will be activated. 

Activating User Password : 

This menu is used for activating the user password. 

After the user password is activated for entering to the menus; if the 

 

button is pressed for 3 sec., while the instant values are observed, user 

password is required. If the user password is entered wrong device does 

not latch. 

Note:  

Factory default value of user password is 

“0000” 

Press SET button for 3 sec. (trA Fo menu is displayed.) 

Press SET button 

(Pın ACt IUA tE menu is

displayed.) 

Press SET button. First digit blinks.

By using UP/DOWN buttons enter the values for blinking digit. By using 

SET button, switch the other digits. Use BACK button to switch the 

previous digit. After setting the last digit, press the SET button, “Pın ACt 

oF” is displayed. “on” can be selected by using UP/DOWN buttons. (Data 

is entered but is not activated yet. For activating the new data please 

follow the below steps.) 

Displaylerde (SAU E SEt yES) görününceye kadar ESC tuşuna tek tek 

basın.

Displaylerde (SAU E SEt yES) göründüğünde SET tuşuna basın

(SAU E SEt yES göründüğünde ESC tuşuna basarsanız veya “yES” 

yerine “no” seçeneğini seçerseniz yeni ayarlar kaydedilmeden ayar 

menüsünden çıkılır. Cihaz önceki ayarlarıyla çalışmaya devam eder.)

3

Summary of Contents for MPR-53CS

Page 1: ...selected 1 out 1 and 2 out 2 for output device gives alarm Related contact outputs will close and LEDs will be on Total Hours Shows running time of MPR 53CS from the beginning User can not reset this...

Page 2: ...will be cancelled and previous value will be activated NETWORK ANALYZER MPR 53CS Current Transformer Ratio Setup In this menu current transformer ratio is set There is no in CT 25 models Current tran...

Page 3: ...s Press ESC button one by one until SAU E SEt yES is displayed When SAU E SEt yES is displayed press SET button If you press ESC button or choose no option instead of yES option by using UP DOWN butto...

Page 4: ...onditions are set When hoU r ACT on is chosen the run hour keeps working uncondi tionally is active When hoU r ACT 2 is chosen the run hour runs if second digital input is active When hoU r ACT ALL is...

Page 5: ...tandart MODBUS RTU message is shown below The T times corresponds to a time in which data must not be exchanged on the communication bus to allow the connected devices to recognize the end of one mes...

Page 6: ...BY USING REPEATER PK 26 Box Connection Diagram 3 Phase neutral 3 Phase without neutral Note For CT 25 models k When CT 25 is used Red cable is connected to k terminal l When CT 25 is used Black cable...

Page 7: ...e neutral 3 Phase without neutral Note For CT 25 models k When CT 25 is used Red cable is connected to k terminal l When CT 25 is used Black cable is connected to l terminal 3 Phase without neutral cu...

Page 8: ...Settings Transformer Ctr Current Transformer Ratio 0001 trn Turn number for CT 25 01 Utr Voltage Transformer Ratio 0001 0 CAL Calculation Method 1 Pin 0000 Not Activated RS 485 Adr Address 1 Bau Baud...

Page 9: ...al in digital inputs It does not run if there is no signal in digital inputs Betriebsstunden Es zeigt die Betriebsstunden Im Gegensatz zu der Gesamtstunden k nnen die Betriebsstunden r ckgestellt und...

Page 10: ...hlt werden Dr cken Sie auf SET Taste f r 3 Sekunden trA Fo Men ist angezeigt Dr cken Sie auf SET Taste TrA Fo Ctr Men ist angezeigt Sie das CAL CUL At on Men blinkelt Mit AUF oder AB Tasten w hlen Si...

Page 11: ...n aber sind noch nicht aktiviert F r die Aktivierung der eingegebenen Daten befolgen Sie die folgende Schritten Dr cken Sie auf ESC Taste bis SAU E SEt yES ist angezeigt Dr cken Sie auf SET Taste W hr...

Page 12: ...oUr ACt 1 ausgew hlt ist funktioniert die Betriebsstunden nur wenn der Digitaleingang 1 aktiv ist Falls hoUr ACt 2 ausgew hlt ist funktioniert die Betriebsstunden nur wenn der Digitaleingang 2 aktiv i...

Page 13: ...Zeit zwischen 3 5 Zeichen Zeit in denen keine Daten ber die Kommunikations Bus ausgetauscht werden m ssen damit die angeschlossenen Ger te die Ende einer Nachricht und dem Beginn eines anderen zu erk...

Page 14: ...HLIESSEN PK 26 Kassenanschlussplan 3 Phasen ohne Neutral Anschluss Nur g ltig f r MPR 53S k Wenn CT 25 benutzt ist rotes Kabel ist an der Klemme k angeschlossen l Wenn CT 25 benutzt ist schwarzes Kabe...

Page 15: ...Kassenanschlussplan 3 Phasen mit Neutral Anschluss 3 Phasen ohne Neutral Anschluss Nur g ltig f r MPR 53S k Wenn CT 25 benutzt ist rotes Kabel ist an der Klemme k angeschlossen l Wenn CT 25 benutzt i...

Page 16: ...gen Die Nichteinhaltung dieser Anweisungen f hrt zu schweren Verletzungen oder zum Tod Vor der Installation entfernen Sie die Leistungsenergie an den Ger ten Wenn das Ger t an das Netzwerk verbindet i...

Reviews: