“CAL CUL Atı on” menu.
Press SET button (Most right digit of 5th display blinks)
By using UP/DOWN buttons select energy calculation method.
Press SET button, “CAL CUL Atı on” is displayed. (Data is entered but is
not activated yet, for activating new data please follow below steps.)
Press ESC button one by one until “SAU E SEt yES” is displayed.
When “SAU E SEt yES” is displayed, press SET button (When “SAU E
SEt yES” is displayed. If you press ESC button or choose “no” option
instead of “yES” option, new data will be cancelled and previous value
will be activated).
Max. Demand Time Setup:
In this menu, Max. demand time is set between 01 - 60 minutes.
Press SET button for 3 sec. (trA Fo menu is displayed.)
Press SET button (Most right digit of 5th display blinks)
By using UP/DOWN buttons, blinking digit value can be programmed.
By using SET button, switch respectively to the digits. Use BACK button
go to go previous digit. After you entered last digit, press SET button,
“de tı” is displayed in the display. (Data is entered but is not activated
yet. For activating new data please follow the below steps.)
Press ESC button one by one until “SAU E SEt yES” is displayed.
When “SAU E SEt yES” is displayed, press SET button (When
“SAU E SEt yES” is displayed. If you press ESC button or choose “no”
option instead of “yES” option, new data will be cancelled and previous
value will be activated).
Reset Menu (hL, dE, E-1, E-2, C-1, C-2, rUn hoUr, SP hoU r):
In this menu value of min., max., max. demand, energy values, pulse
counters, run hour and alarm clock are erased. It saves the instant
measured min., max., max. demand energy values, the devices running
time, time after the device is setted into its memory. In this menu when
you enter “rES Et hL/dE/E-1/E-2/C-1/C-2/rUn hoUr/SP hoU r” menu
changes all the values are erased at the same time.
Note:
from power cut.
Reset Menu (hL, dE, E-1, E-2, C-1, C-2, rUn hoUr, SP hoU r):
Press SET button for 3 sec. (trA Fo menu is displayed.)
Press SET button (rES Et hL menu is
displayed.)
By using UP/DOWN buttons “rES Et hL/dE/E-1/E-2/C-1/C-2/
rUn hoU r/SP hoU r” menu.
Press SET button (rES Et hL/dE/E-1/E-2/C-1/C-2/rUn hoU r/
SP hoU r is displayed).
By using UP/DOWN buttons, if you want to delete, the min., max., max.
demand, energy values, the running time of the device and the running
time after the device is set; select “yES” otherwise select “no” option.
Press SET button, “rES Et hL/dE/E-1/E-2/C-1/C-2/rUn hoU r/SP hoU r”
is displayed. (Data is entered but is not activated yet. For activating new
data please follow the below steps)
Press ESC button one by one until “SAU E SEt yES” is displayed.
When “SAU E SEt yES” is displayed, press SET button (When “SAU E
SEt yES” is displayed. If you press ESC button or choose “no” option
instead of “yES” option, new data will be cancelled and previous value
will be activated).
NETWORK ANALYZER
MPR-53CS
Current Transformer Ratio Setup:
In this menu current transformer ratio is set (There is no in CT-25
models).
Current transformer ratio can be set between 1 ..... 2000.
Note: If the current transformer is not used between the system and the
device, current transformer ratio is entered as “1”.
Example: If between the device and the system there is a 30A/5A current
transformer is used;
Current transformer ratio = 30/5 = 6 must be setup.
Press SET button for 3 sec. (trA Fo menu is displayed)
Press SET button, trA Fo Ctr menu is displayed (For CT-25 models
trA Fo trn menu is displayed).
(Note: trA Fo Utr / Con nEC tıo n menu can be displayed by scrolling UP/
DOWN buttons.)
(trA Fo Utr or Con nEC tıo n menus can be programmed similarly.)
Using the UP/DOWN buttons and program the blinking digit. Switch
to other digits by using SET button, use BACK button to go topevious
digit. After programming last digit press SET button, “trA Fo Ctr” is
displayed. (Data is entered but is not activated yet. For activating new
data please follow the below steps.)
Press ESC button one by one until “SAU E SEt yES” is displayed on
display.
When “SAU E SEt yES” is displayed, press SET button. If you press ESC
button or choose “no” option instead of “yES” option by using UP/DOWN
buttons, new data will be cancelled and previous value will be activated.
Entering Turn Number:
This menu is available for CT-25 adapted devices. Turn number is chosen
from CT-25 current transformer (How many tour the current cable has
rounded). The values between 1 and 20 can be written. Greater the
number of turn means greater the sensivity.
Voltage Transformer Ratio Setup:
In this menu, voltage transformer ratio setup is set.
Voltage Transformer ratio is set between 0000,1 - 4000,0.
Note:
If the voltage transformer is not used between the system and the
device. The voltage transformwer ratio is entered as “1”.
Example:
Between the voltage transformer and the device, if there is a
34,5KV/100V voltage transformer is used;
Voltage transformer ratio = 34500/100 = 345 can be entered.
Chosing connection option:
In this menu connection option is selected. There are 2 option as
“delta” and “star”.
When “Star” connection is chosen, the device makes a protection
between phase-neutral for voltage.
When “Delta” connection is chosen, the device makes a protection
between phase-phase for voltage.
NOTE: When “Delta” is chosen Neutral Current (I
N
) and
Phase-Neutral Voltage (V
LN
) values can not be shown in instant
values. Functions that belong to this parameters are inactive.
Reactive Energy Calculation Method Settings:
Informations about Reactive energy calculation method is explained in
below table. The method of active and reactive energy calculation of
mechanic and electrical counters must be chosen from the table.
Press SET button for 3 sec. (trA Fo menu is displayed.)
Press SET button (TrA Fo Ctr menu is displayed.)
2