Function Diagram

PHASE FAILURE DEVICES

MK-05 / 05P / 06 / 06P, MKC-05 / 05P / 06 / 06P

1. On LED
2. Out LED
3. Phase sequence fault LED
4. Asymmetry fault LED
   (While LED no. 3 and 4 are ON at the
   same time, it means there is phase
   failure)
5. Contact ( 3 ) NO connection of output relay
6. Contact  (2 ) common connection of
    output relay

7. Contact (1) NC connection of output relay
8. Time adjusment (0.1 sec.-10 sec.)
9. Asymmetry adjusment (5%-15%)
10. L1, L2, L3 phase connection
11. Neutral connection
     (Only for 05 and 05P series)
12. PTC connection*
*: Only available in MK-05P,MKC-05P If
PTC is not used in MK-06P, MKC-06P by
any reason, the PTC terminals should be
short circuited.

Connection Diagrams

General

One of the common faults faced in industrial plants is overheating and damaging

of 3 phase motors due to the phase failure. “Thermic-magnetic device” which is an

essential element in motor protection is generally too slow due to both its

electromechanical structure and the use of hing current setting range to assure

demarrage without tripping. Being designed to eliminate the above disadvantages,

MK-05, MKC-05, MKC-06 and MK-06 Phase Failure Devices serve the following

protection features

Technical Data

Rated Voltage (Un)

:  220 VAC (For MK-05/05P, MKC-05/05P)

3 phase + neutral, 4 wires connection

120 VAC (MKC-05/05P Custom design)

3 phase + neutral, 4 wires connection

380 VAC (For MK-06/06P, MKC-06/06P)

3 phase, 3 wires connection

440 VAC (MKC-06/06P Special design)

3 phase, 3 wires connection

220 VAC (MKC-06/06P Special design)
3 phase, 3 wires connection

The three phase network being protected is used as the device power

supply.

Operating Range

: (0.9-1.1) x Un

Rated Frequency

: 50/60 Hz

Output Contacts

:1 C/O with 8A, 2000 VA, Cos

j

=1

Asymmetry Range

: 5% - 15%; 3 x 380 VAC

Tripping Time

: 0.1 - 10 sec. (adjustable)

Phase Sequence

: Available

Ambient Temperature

: -5 oC to + 50 oC

Protection Class

: IP 20

Diemensions

: Type PK 21 (For MK-05/05P, MK-06/06P)
  Type PK 25 (For MKC-05/05P, MKC-06/06P)

Installation

: Surface mounting or on the mounting rails

Weight

: 0.3 kg (For MK-05/05P, MK-06/06P)
  0.2 kg (For MKC-05/05P/06/06P)

Precautions For Installation and Safe Use

Failure to follow those instructions will result in death or serious injury.
  Disconnect all power before working on equipment.
  When the device is connected to the network, do not remove the front panel.
  Do not try to clean the device with solvent or the like. Only clean the device
  with a dried cloth.
  Verify correct terminal connections when wiring.
  Electrical equipment should be serviced only by your compedent seller.
  Mount device to the panel.

A2910 / Rev.8

1. Voltage Unbalance (Adjustable)

    Unbalanced voltage may occured when;

    The mains are loaded with unbalanced distribution,

    One of the 3-phase of motor has lost. In this case, some amount of voltage which

produced by other phases will be inducted on the lost phase. Amount of this value

depends on both the motor type and amount of load.

Output relay is activated when a phase has lost or an unbalanced Phase-Phase

voltage value, which is occured with any reason, is smaller than the user defined

asymetrical value. If this unbalanced voltage value exceeds the adjusted asymetrical

value (5-15%); output relay will release itself and switches off the motor at the end

of adjusted time delay (0.1-10 sec.); Relay’s LED is turned off. Asymetry error LED

is turned ON. If the fault has gone within the delay time, the output relay is remoined

and will not switch off the motor.

    In Applications; a proper asymetrical value should be adjusted regarding to the

inducted voltage value in two-phase which are remained after the other one has

lost.

The voltage asymmetry causes the rise in motor temperature and a reduction of
the rated motor power.

Voltage asymmetry limit values are adjusted (5%-15%) by the user.

Hysteresis is fixed at 20%.

Example: Given 3x380 V supply with 10% asymmetry,

Relay switches OFF at: 380-(380 x10%)=342 V

Relay switches ON at: 342 + (342 x 10% x 20%)=348.8 V

2. Phase Sequence

When the phase sequence is correct (L1, L2, L3 in clockwise direction) the output

relay is activated; however, if the sequence is changed by any reason, the output

relay switches OFF immediately. Relay LED is OFF, Phase Sequence error LED is

ON.

3.PTC Protection (Only Available in MK-05P, MKC-05P,

MKC-06P &  MK-06P versions)

When the coil  temperature in motors exceeds Tc, the limit temperature of PTC, the

output relay switches off immediately, Relay LED is OFF. This feature is included

only in MK-05P,MKC-05P,MK-06P and MKC-06P. See following figure for typical

resistance of PTC vs temperature characteristics for three different swiching

temperatures (110 oC, 120 oC, 130 oC). Normally,     PT-110 is used and it can be

changed upon request.

5. Insufficient Supply

L1 is the supply phase of the  MK-05 and MK-05P in PK21 package while L3 is the

suply phase of MKC-05 and MKC-05P devices. For MK and MKC devices if supply

voltage falls below 60-65% of rated voltage, output relay switches off without delay

and error leds start to blink one after another sequentially.

TYPE PK21

35

80

44

80

14

35 mm

90 mm

45 mm

62 mm

58 mm

32 mm

48 mm

35 mm

TYPE PK25

*

C1

T1

Stop

T1

N

M

3 ~

PTC

Start

L1
L2
L3

N

C1

3

2

1

N

L1

L2

L3

PTC

*

C1

T1

Stop

T1

M

3 ~

PTC

Start

L1
L2
L3

C1

3

2

1

L1

L2

L3

1

2

3

PTC

3

2

1

L1

L2

L3

1

2

3

PTC

5

6

7

12

9

3

8

2
1

4

10

*

3

2

1

N

L1

L2

L3

PTC

5

6

7

12

9

3

8

2
1

4

11

10

*

*

5 6 7 12

1

2

3

4

11

10

8

9

3

2

1

1

3

2

N

L1

L2

L3

10

15

10

5

0.1

4

6

8

PTC

MK-05/05P

Phase Failure

Device

t(sec.)

%

Asym.

Phs. Seq.

Asym.

Output

On

Phs.

Fail

*

5 6 7 12

1

2

3

4

10

8

9

3

2

1

1

3

2

L1

L2

L3

10

15

10

5

0.1

4

6

8

PTC

MK-06/06P

Phase Failure

Device

t(sec.)

%

Asym.

Phs. Seq.

Asym.

Output

On

Phs.

Fail

1

2

3

1

2

3

Asm.

Phs.

Seq.

Phs.

Fail.

Out

On

MKC-06/06P

 5

15

10

  %
Asm.

10

8

6

4

2

0.1

t(s)

Asm.

Phs.

Seq.

Phs.

Fail.

Out

On

MKC-05/05P

 5

15

10

  %
Asm.

10

8

6

4

2

0.1

t(s)

Asm.

Phs.

Seq.

Phs.

Fail.

Out

On

MKC-06/06P

 5

15

10

  %
Asm.

10

8

6

4

2

0.1

t(s)

Asm.

Phs.

Seq.

Phs.

Fail.

Out

On

MKC-05/05P

 5

15

10

  %
Asm.

10

8

6

4

2

0.1

t(s)

No responsibility is assured by the manufacturer or any of its subsidiaries

for any consequences arising out of the use of this material.

Adjusted unbalance value

Hysterisis

L1

L2

L3

Output Relay

TD = Tripping Time

TD

TD

Wrong phase sequence

N

Reviews: