© COPYRIGHT 2016 ENTERGIZE, LLC.  ALL RIGHTS RESERVED.

      

P/N 71969 3220-2345  REV 00=E

3

MENU

 

FEATURE

OPTIONS

STD. DEFAULT DESCRIPTION / COMMENTS

170

Remote Sensor

0-8

0

Select sensor if used. Contact PECO for information on the T8000 Series Indoor Remote Zone Sensor.

0 =   No Remote Sensors 

1 =   Remote Indoor Sensor Only

2 =   Not Used

3 =   Not Used 

4 =   Not Used

5 =     Not Used

6 =     S3 Input with Aquastat Only

7 =     S3 Input with Aquastat and S1 with Remote Indoor Sensor

8 =     Not Used

171

Sensor Average 

Remote & Local

0 – Local/Remote 

1 – Average 

Local/Remote

This feature allows both local and remote sensing. SM 170 must be set to either 01 or 07.

240

Number of Program 

Periods

2; 4 events

4

2 =   2 events per day (Selections OCC1 and UnOcc1)

4 =   4 events per day (Selections Occ1-UnOcc1-Occ2- UnOcc2)

250

Clock Format

12 or 24 Hours

12

12 =   12-hour clock mode

24 =   24-hour clock mode

260

Temperature Format 

(°F or °C)

0,1

1

0 =   Celsius

1 =   Fahrenheit 

265

Single/Dual Setpoint

0,1

1

Determines if single user override setpoint is used, or if user sets heat and cool setpoints independently.

0 =   Dual Setpoint (Heat and Cool)

1 =   Single Override Setpoint (Single  Setpoint with auto changeover algorithm)  

290

Range Low

50-90 °F or 

10-32°C

50°F

Choose the lowest selectable temperature setpoint value.

300

Range High

50-90 °F or 

10-32°C

90°F

Choose the highest selectable temperature setpoint value.

310

Setback Low

Off; 50-82°F

67°F

Temperature setpoint thermostat will Heat to when in Setback mode (Off sets Heating to ~45F Setback).

0 =   Off ;  50-82°F (11-27°C) 

320

Setback High

Off; 58-90°F

78°F

Temperature setpoint thermostat will Cool to when in Setback mode. (Off sets Cooling to ~150F in 

Setback). 

0 =   Off (disabled)

58-90°F (11-32°C)

325

Occupied Sensor 

Operation

0-1

1

0 =   Disabled

1 =   Occupancy Operation ON

326

Occupied Timer 

Duration

30 min; 1, 2 ,4, 6 

8,16,20, 24 hrs 

2 hrs

Sets the time required to go into setback after last detection.        

327

Setback Ramping

0, 1, 2

1        

Determines how fast the control will setback.  

0 =   Economy (No delay)

1 =   Comfort 1 (1 °F per hour)

2 =   Comfort 2°(2 °F per hour)

328

Nighttime Lock On

0-1

0

Locks the thermostat to Occupied mode after 10:00pm. Thermostat resets at 08:00am.  

NOTE: This feature requires the clock time to be set.  

0 =   Disabled

1 =   ON

330

Zone Temp Offset

 +/-9°F or +/-

4.5°C

0°F

340

Keypad Lockout

0-3

0

Restricts access to certain features of device; Service Menu still available if keypad lockout is enabled.

0 =   No key pad lockout (Default)

1 =   Disables Schedule and System keys

2 =   Disables Schedule, System, and Fan keys

3 =   Disables all keys

341

Enable Pin Access

0,1

0

Applies a 3 digit  access code to enter Service Menu 342
0 =  Disable  

1 =   Enable

342

Set PIN   

000-999

000

Choose a 3-digit  PIN access code. 

350

Fan Mode

1-3

3

1 =    ON: Fan is always on, regardless of demand
2 =   Auto: Fan is only on with heating or cooling demand
3 =   ON or Auto: Occupant can choose either selection 

360

System Mode

0-3

1

Allows ability to determine which system modes the occupant can select. 
0 =  OFF, Auto
1 =   OFF, Heat, Cool, Auto
2 =   OFF, Heat, Cool
3 =   Heat, Cool, Auto

Summary of Contents for T8532OCC

Page 1: ...ectrostatic discharge to thermostat CAUTION Do not connect unused wires together ALL ELECTRICAL LOADS MUST BE CONNECTED TO TERMINAL C 24 VAC TABLE 1 TERMINAL BLOCK Fan Coil Conventional Heat Pump C 24 VAC Unswitched side C 24 VAC Unswitched side W1 Stage 1 Heat B O Reversing Valve W2 Stage 2 Heat AUX Auxiliary Heat Stage 2 or 3 G FAN High G FAN High A FAN Medium A FAN Medium E FAN Low E FAN Low Y1...

Page 2: ...F 18 to 49 C MENU FEATURE OPTIONS STD DEFAULT DESCRIPTION COMMENTS 100 Schedule Format 0 3 1 Select the schedule format on the T8000 Series Menu not available on non programmable thermostats NOTE Set the clock before changing to non progammable 0 nonprogrammable 1 programmable 2 5 1 1 schedule 3 5 2 schedule 101 Daylight Saving Time 0 1 0 Select daylight saving time as it follows standard format i...

Page 3: ...etpoint thermostat will Heat to when in Setback mode Off sets Heating to 45F Setback 0 Off 50 82 F 11 27 C 320 Setback High Off 58 90 F 78 F Temperature setpoint thermostat will Cool to when in Setback mode Off sets Cooling to 150F in Setback 0 Off disabled 58 90 F 11 32 C 325 Occupied Sensor Operation 0 1 1 0 Disabled 1 Occupancy Operation ON 326 Occupied Timer Duration 30 min 1 2 4 6 8 16 20 24 ...

Page 4: ...nd 502 501 Intermittent Fan On Time 1 60 minutes 5 minutes 502 Intermittent Fan Off Time 0 60 minutes 25 minutes A selection of 0 will result in continuous Fan 520 Default Display Icons 0 4 0 Select icons that will be displayed in the Default Display screen 0 Time Temp SP 1 Time Temp 2 Time only 3 Temp only 4 No Display 530 Revision displayed 540 Factory Default Reset 0 1 0 When Enable is selected...

Reviews: