393930-2 Rev 0: 01.04.2020
12 |
P a g e
Sub-menu for cooling recovery
Maximum rotor exchange speed Range 0% . 100%; default 100%
4.3.1
Cooker hood function
The air handling unit has a digital input for the cooker hood.
When the signal is active, the Supply and Extract fan speeds are
set to the specified speeds in 0-100%
Duration of the fan speeds after signal has disappeared. Range 00:00 (only
run when active signal);
1 min .. 1 hour 30 min; default 0 min
Supply fan speed during active cooker hood signal Range 0 – 100%; default
100%
Extract fan speed during active cooker hood signal Range 0 – 100%; default
100%
4.3.2
Cooling recovery function
Cooling recovery is used when the intake air temperature is
higher than the room temperature to keep the rooms cool.
Turn the cooling recovery mode On or Off Default
Off
Activate cooling recovery when the intake air temperature is
2
⁰
C or 3
⁰
C higher than the room temperature.
Range 2
⁰
C or 3
⁰
C