14 / 24

L2

L1

L3

6.2.1. Dynamic Load Management (DLM)

You can implement dynamic load management with for this purpose compatible energy meter. The figure 

below shows an example how you can build up the system.
• 

The energy meter measures the total power consumption and the actual current per phase. If some 

other load over the set maximum current for load management is added when charging is ongoing, 

the charger will decrease the charging current. If the total power consumption reaches the allowed 

maximum power, the charging interrupts untill the the total power consumption has decreased to a 

value at which the charging can continue.

• 

Use only current transformers which have the same serial number, they are calibrated with one an-

other. 

• 

1-phase measurement: select the correct parameters in the energy meter’s settings.

• 

Please see the energy meter instructions for more detailed information.

Main fuse

Energy

meter

Other loads

EVH...

EV

Power supply

RS-485

L1       L2      L3

Switchboard

Summary of Contents for One Home EVH161B-HC000

Page 1: ...ENG RAK131B_ENG 2022 10 14 2022 Ensto Chago Installation Manual Ensto One Home...

Page 2: ...f charging in Override mode 16 7 Technical information 17 8 Code key 19 9 Installation Commissioning checklist 20 10 Dimension drawing 21 11 Troubleshooting 21 12 Charger Control Application 22 12 1 P...

Page 3: ...or user from responsibility to obey all applicable safety regulations This Installation Manual is a part of the product and must be stored in a safe location so that it is available for future install...

Page 4: ...umans and animals from electric shock RDC DD Residual Direct Current Detecting Device RS 485 Recommended Standard 485 standard defining the electrical characteristics of driv ers and receivers for use...

Page 5: ...station from its package Do not scratch the surface of the charging station after removal from the package When selecting installation site take into account the following The charging station is suit...

Page 6: ...arging station If it is necessary to open additional cable entries you have to disassemble the charging station Installation steps when cable routing is from alternative cable entries 1 Disassemble th...

Page 7: ...gasket for cable 12 24mm 2 Open the necessary cable entries with a step drill bit M16 cable entries are suitable for the RS 485 or dry contact cablings 3 Prepare the cable entries with suitable access...

Page 8: ...terial suitable screws 2 Fasten the upper screw 1270 mm measured from the ground sur face The plug holder will be at a height of 1200 mm 5 3 Wall mounting When selecting the installation location make...

Page 9: ...cal cables approx 150mm through the cable glands 8 Cut the supply cable conductors in suitable lengths Leave the ground conductor long enough so that if a fault occurs it is the last one that comes lo...

Page 10: ...with the charging station For more information see the User Guide chapter 14 Charger Control Application on pages 5 8 Settings intended for qualified professionals only see the chapter 12 Charger Cont...

Page 11: ...hese charging station models to an IT network L1 L2 L3 L1 N PE EVH161B HCR00 EVH321B HCR00 A combined device with residual current circuit breaker and over current protection RCBO is integrated A labe...

Page 12: ...ot work Do not connect these charging station models to an IT network PE 1 3 5 N 2 4 6 N QF1 Energy meter Supported energy meter EVHEM217 Carlo Gavazzi EM2172RVV23XOSX Connect the energy meter to term...

Page 13: ...emove the jumper from the pre installed connector Note If you do not connect a dry contact module to the charging station do not remove the jumper or change the related settings in the Charger Control...

Page 14: ...n charging is ongoing the charger will decrease the charging current If the total power consumption reaches the allowed maximum power the charging interrupts untill the the total power consumption has...

Page 15: ...Connected Contactor The Connected Contactor switches off the charging current When the Connected Contactor gets a signal that the total power consumption has decreased to a set value it switches on th...

Page 16: ...le how you can build up the override control of charging with a timer switch relay or similar When the dry contact is closed the charging station gets power and can charge the connected vehicle When t...

Page 17: ...3B HC000 EVH161B HCR00 EVH163B HCR00 EVH321B HCR00 EVH323B HCR00 Material Polycarbonate Color Frame RAL7021 dark grey Cover Silver Installation box Screw fixing Mechanical hatch lock Weight approx 7 k...

Page 18: ...distribution board Leakage detection integrated RDC DD 6mA Residual current circuit breaker and over current protection integrated RCBO 30mA Miniature circuit breaker MCB Max 16A must be installed in...

Page 19: ...socket Not available M MID class kWH meter Not available R RCBO Fixed charging cable 2 Type 2 socket T2 S Type 2 Shutter socket T2S Home A Apartment Product version B load management 1 phase 3 3 phase...

Page 20: ...ng cable size protective devices Review the local electrical design plan The PE cable screw is tight The power supply conductors L1 L2 L3 N and PE are properly connected The insulation of the power su...

Page 21: ...action Mains voltage does not exist in supply connec tors L1 L2 L3 Make sure that the supply conductors are properly connected Make sure that there is power available The circuit breaker QF1 is off E...

Page 22: ...station Note Do not change the settings while charging is in progress 12 2 1 Technical max charging current Maximum current that the electrical supply of the property can provide to the charging stati...

Page 23: ...is stable green during the self test The extent and duration of the self test depend on the charging station model If a critical fault is detected during the self test the charging station will go to...

Page 24: ...Ensto Chago Oy Ensio Miettisen katu 2 P O Box 77 FIN 06101 Porvoo Finland Tel 358 204 76 21 www ensto com building systems...

Reviews: