Connecting the external indicator light housing
The LYNX 4400's indicator light housing has red and green lights. It is supplied with a 3X1.5mm²
U1000RO2V type cable. Position the indicator light with the cable gland facing downwards.
Connect the J9 terminal block as follows:
Te: Brown wire
Terminal V: Black wire
Terminal R: Grey (or blue) wire
+ V R
Connecting to remote indication
The connection is made using a 4X1.5mm² U1000RO2V type cable -
not supplied
An equipment fault may be actuated by the detector in response to:
- A need to replace the battery or batteries when the battery becomes flat after 7.5 years of use
- An anomaly affecting the alternative auxiliary power supply
- An anomaly affecting the electronics
Connect the J5 terminal block (removable and screwed-in) as follows:
Power supplies (depending on the option)
LV power supercapacitor option 350 Farad 2.7 V supercapacitor - Usable life 15 years
Standalone option: 2 x D20 LSH 20 type lithium batteries, not supplied - Usable life: ≥ 7.5 years
Note: the two batteries face in the same direction
(+ to the left)
.
NC NC R V DE C
Terminals NC: Not connected
Terminal R: Red fault
Terminal V: Green fault
Terminal DE: Equipment fault
Terminal C: Common