NO. NX2010597/ NO. 72983_C
06/04/2021
13 (35)
4P
R
-F
14
-D
Modular MV cell
Compact MV cell
Protective shield
Green side
Earth for
cable shields
and the
IP2X connector for the cores
cores' S2s
Each core is mounted on a phase of the underground cable, with the green side facing towards the unit's
busbar.
It is centred and attached to the cable using 3 self-centring rubber bosses.
THE SCREENED BRAID FOR EACH PHASE MUST BE CREATED BY AN INSULATED CONDUCTOR AND
PASSED INSIDE THE CORRESPONDING CORE.
The wires for each core are connected using a coded 2-contact MATE-N-LOCK connector.
A 4x1.5mm² U1000RO2V type cable equipped with female MATE-N-LOCK connectors is supplied for
connecting cores to the LYNX 4400's J2 terminal block.
Insert the stripped end with end sleeves into the LYNX's cable grommet.
Connect the J2 terminal block as follows:
l1 l2 l3 C NC
Terminal I1: Brown wire
Terminal I2: Black wire
Terminal I3: Grey wire
Terminal C: Blue wire (common)
NC terminal: Not connected
Green side
Earth for cable
shields and the
cores' S2s
Core IP2X connector