1. GENERAL INFORMATION
All-round luminaire for wet and dry conditions suitable for work point illumination e.g. in
kitchen, utility room, bath room, hobby room and at other work point places. The luminaire body is of
white painted aluminium. The body ends and diffuser are of impact resistant polycarbonate.
ONLY A PROFESSIONAL ELECTRICIAN IS ALLOWED TO DO THE INSTALLATION. USE ONLY STARTERS,
LIGHT SOURCES AND RATED WATTAGES AS MARKED IN THE LUMINAIRE.
SWITCH OFF THE CURRENT BEFORE INSTALLATION OR SERVICE.
THIS INSTALLATION INSTRUCTION MUST BE KEPT AVAILABLE FOR FUTURE MAINTENANCE.
N.B. WHEN THE T5 - FLUORESCENT LAMP IS IN VERTICAL POSITION PUT IT WITH THE MARKED
SIDE DOWN.
LUMINARIES PROVIDED WITH AN ELECTRONIC BALLAST E, D, DB AND DD MUST ALWAYS BE EARTHED.
When a thin control cable is used and it is necessary to reach IP-44 class, an additional gasket must be used.
2. MOUNTING AND SERVICE
The diffuser is removed by pressing the lower edges of the diffuser’s ends inwards and at the same time
pulling the diffuser outwards. The protection cover is removed by loosening the fastening screw and
moving the plate sideways in which case it can be lifted away. If necessary to release condensed water
bore a Ø 5 mm hole when ceiling mounted in the middle and when wall mounted in the lower part of the
diffuser.
FASTENING, pic. 1 and 2.
The luminaire is for surface mounting on wall, corner or ceiling. Fasten the luminaire to the mounting base
with the screws and the semi-protection gaskets through the body. The holes for fixing are bigger than the
Ø of the screws, giving 4 mm adjusting at the fastening.
WIRING, pic. 1a
Connect the neutral conductor (blue) to the terminal N, the earth conductor (yellow-green striped) to the
terminal and the phase conductor (black or brown) to the terminal 1. When the luminaire with socket
outlet is chained the supply cable has to be connected to the main terminal of the luminaire. The terminals
1 and 2 are ready-connected. If the socket is supplied separately, connect the supply to the terminal 2 and
at the same time remove the loop connecting the terminals 1 and 2.
DUST COVER OF THE SOCKET OUTLET, pic. 1b.
If IP44 class is not required, the cover of the socket outlet can be removed and the hole/space can be
covered by a special covering-piece in, which case the IP class is 21 (see picture 1).
MODELS THAT ARE EQUIPPED WITH THE RESIDUAL CURRENT CIRCUIT BREAKER, AVR…WP, pic. 3):
The models are equipped with the 25A/30mA. residual current circuit breaker for the socket outlet .
Test the operation of the residual current circuit breaker once a month by pressing the test button.
In that case the residual current circuit breaker will go off. It is returned by turning the switch to
position I.
The warranty period for luminaries is 3 years from the date of purchase but no longer than 4 years from
the date of manufacture. Warranty does not cover light sources. Warranty conditions, see
www.ensto.com.