- 10 -
2) Cables & Materials
Name
Specification
Quantity
Power supply cable
≧
5*6mm
²
three-phase power supply cable
Depend on actual requirement
Network cable
STP, Category 5 enhanced, 8 cores
Depend on actual requirement
Network cable plug
RJ45
Depend on actual requirement
Insulated tape
0.15mm*18mm, 0~600V, 0
℃
~80
℃
Depend on actual requirement
Cable tie
4*200mm
Depend on actual requirement
2.1.3 Installation Process
1) Installation Notice
a)
Electrical device should be installed, operated, serviced, and maintained only by qualified personnel. No
responsibility is assumed by the manufacturer for any consequences arising out of the use of this device.
A
qualified person is one who has skills and knowledge related to the construction, installation and operation of
electrical device and who has received safety training to recognize and avoid the hazards involved.
b) All applicable local, regional, and national regulations must be respected when installing, repairing, and
maintaining this device.
2) Layout Cables
Wall-mount Installation
:
Network cable and power supply cable inlet
from the top, fixed with cable slot.
Cable slot lays on the wall against the center line
of parking place. Cable slot end should be above
the ground at 1.3cm.
Cables extend out of the slot end with more than
30cm.
Floor-stand Installation
:
Locate the position for floor-stand pillar on the
ground, against the center line of parking place.
Bury network cable and power supply cable
under the ground.
Cables go out of the ground from the position of
floor-stand pillar with more than 150cm.