To enter commissioning mode, start by selecting one button contact of PTM 216B. Any but-
ton of PTM 216B (A0, A1, B0, B1) can be used. This button is referred to as
Button_X
in
Figure 20 above.
Next, execute the following long-short-long sequence:
1.
Press and hold the selected button together with the energy bar for more than 7
seconds before releasing it
2.
Press the selected button together with the energy bar quickly (hold for less than 2
seconds)
3.
Press and hold the selected button together with the energy bar again for more than
7 seconds before releasing it
Upon detection of this sequence, PTM 216B will enter commissioning mode if the
DISABLE
LRN TELEGRAM
flag in the
Configuration
register of the NFC interface is not set (
0b0,
default
state).
If the
DISABLE LRN TELEGRAM
flag in the
Configuration
register of the NFC interface is set
(
0b1,
configured via NFC interface) then PTM 216B will not enter commissioning mode and
transmit normal data telegrams according to the button status.
5.3.2
Commissioning telegram transmission
PTM 216B will transmit a commissioning telegram (on the radio channels selected as de-
scribed in chapter 3.1) upon entering commissioning mode. The structure of the commis-
sioning telegram is described in chapter 4.6.3.
PTM 216B will continue to transmit commissioning telegrams whenever the button used for
entry into commissioning mode (
Button_X)
is pressed or released again.
5.3.3
Exit from commissioning mode
Pressing any key except the button used for entry into commissioning mode (
Button_X
) will
cause PTM 216B to stop transmitting commissioning telegrams and return to normal data
telegram transmission.
5.3.4
Disable commissioning mode
Starting with product version DC-06 it will be possible to disable commissioning mode in
addition to using the NFC interface also by means of a specific button input.
To do so, press buttons A0, A1 and B1 together with the energy bar and hold them for at
least 10 seconds before releasing them.