![EnOcean LEDD Installation Manual Download Page 8](http://html.mh-extra.com/html/enocean/ledd/ledd_installation-manual_2413721008.webp)
LED Zone Controller 0-10V Installation Guide
© 2017 EnOcean GmbH V2.0
Page 8
P
Parameter
Description
Default /
Notes
System Parameters
MinVoltageLevel
Minimum 0-10V output voltage
level when light is switched ON
1.0V
MaxVoltageLevel
Maximum 0-10V output voltage
level when light is switched ON
10.0V
ModeAfter-
PowerLoss
ModeAfterPowerLoss
(ON/OFF/LAST STATE)
LAST STATE
StatusMessage-
Timer
Defines, how often status messages
are transmitted (seconds, 0=off,
0xFFFF=only event based)
0xFFFF
RepeaterFunction
Defines the repeater level of the
device (OFF/1-Level/2-Level)
OFF (disabled)
RepeatLinked-
DevicesOnly
Configures the repeater to only
repeat telegrams from devices
linked to it
ON (enabled)
Enable-
DebugMessages
Enable or disable debug messages
OFF (disabled)
EnableLink-
Checker
Enable or disable link checker
(if a learn telegram from a linked
device is received while in
operating mode, the 0-10V output
will toggle once between 10% and
90%)
ON (enabled)