background image

LED Zone Controller 0-10V Installation Guide  

© 2017 EnOcean GmbH    V2.0 

 

Page  6 

 

Setting the output light level to 0 will cause the output of 
LEDR to go to OFF state. 
If the light level has been adjusted by the user (by single or 
double click on the “I” button or by brightening / dimming 
via “I” / “O” button), then the selected light level will be 
maintained for a period defined by LlsAdjustmentDelay 
(default 15 minutes).   
After that, LEDR output is adjusted according to the light 
level reported by the light level sensor.  
In five point dimming mode, users can modify the dimming 
curve if LlsEnableCurveAdjustment = ON.  
This is achieved using a fast triple click (<0.7s) on the “I” 
button. Doing so will replace the supporting point matching 
most closely the current reported illumination level with the 
current illumination level and the current 0-10V output level.  
The connected light will blink (0% / 100%) three times to 
acknowledge successful adjustment. Doing that at different 
daylight levels allows defining the whole curve.  
The light level sensor can alternatively be used to activate an 
automatic switching mode between 0% (OFF) and 100% 
(MaxVoltageLevel) based on light intensity (twilight switch). 
This can be achieved by configuring DaylightingMode to  
2-level mode via remote commissioning.  
The thresholds for switching between the two levels are 
defined by PhotoOnThres (output will be set to 
MaxVoltageLevel for reported values below this level) and 
PhotoOffThres (output will be set to MinVoltageLevel for 
reported values above this level).   

 
Repeater function 

The LED controller provides the option to activate one-level 
(repeat only original telegrams) or two-level (repeat original 
telegrams or telegrams that were repeated once) repeater 
mode for EnOcean radio telegrams.  
By default (RepeatLinkedDevicesOnly=ON) only messages 
from linked devices are repeated. Setting this parameter to 0 
will cause all messages to be repeated. 
Note:
 2-level repeating function and repeating of all 
messages (RepeatLinkedDevicesOnly=OFF) should only be 
used if really needed! Otherwise the system function can be 
compromised by collisions of telegrams. 

Status messages 

The LED controller will transmit a status message  
(EEP D2-40-00) after change of its output state or after 
StatusMessageTimer has elapsed.  
By setting StatusMessageTimer to 0 status messages can be 
switched off completely. By setting it to 0xFFFF only event 
based messages will be sent. 

 

 

Central controller 

LEDR can also be connected to a central controller (EEP A5-
38-08). It supports the dimming command 0x02 of this EEP.   
  

7.

 

Troubleshooting 

 

 

Problem 

Solution Checklist 

The device does not power up

 

 

Check the wiring for errors 

 

Check the circuit breaker 

 

Use a voltage meter to confirm 

power

 

Cannot link other devices

 

 

Check if linking mode can be 

accessed 

 

Move closer to the device; it 

may be out of range 

 

Try linking a different device 

 

Check for environmental 

conditions that interfere with 

RF signals 

 

Verify the maximum number of 

devices has not been exceeded 

- 20 switches 

- 10 occupancy sensors 

- 1 light level sensor 

- 1 central controller 

- 1 demand response controller 

The device does not respond to 

wireless messages or selected 

settings

 

 

Check for environment or 

range issues 

 

Verify the device is linked  

 

Check if appropriate devices 

are linked according to good 

system planning 

 

Extend the antenna to amplify 

the range: remove it from the 

groove in the module, and 

straighten it.

 

 

 
Contains:   902 MHz: 

FCC: SZV-STM300U  

 

 

IC: 5713A-STM300U 

 

 

This device complies with part 15 of the FCC rules and Industry Canada ICES-003.  
Operation is subject to the following two conditions: (1) This device may not cause harmful 
interference, and (2) this device must accept any interference received, including interference 
that may cause undesired operation.  
IMPORTANT! Any changes or modifications not expressly approved by the party responsible for 
compliance could void the user’s authority to operate this equipment.  

 

 

Summary of Contents for LEDD

Page 1: ...ntrollers n Installs inside or mounts to electrical box using threaded connector n Supports wireless remote commissioning to link devices and set parameters Specifications typ values Power Supply 11 0 V 13 2 V DC Supply Current typ 16 mA 12VDC supply no sourcing 38 mA 12VDC supply 10V 20mA sourcing Power Consumption 200 mW 12 V DC excluding 0 10V sourcing power 460 mW 12 V DC at maximum 0 10V sour...

Page 2: ...enna as shown in figure A 4 Restore power to the circuit 5 Use the setup interface to link devices and configure settings refer to the Linking Configuration sections WARNING Move the module away from any power line before using the local setup interface 3 Device Configuration The LED controller can be configured in two ways n By user input to the local setup interface This approach is used for bas...

Page 3: ...e will stop after 30 seconds if no LRN telegram is received 2 For the transmitter to be linked do one of the following according to the type of device A Sensor click the designated link button B Rocker Pad click the I button top button marked on the switch plastic or I symbol on the back of the switch 3 times quickly 3 If the device has been linked successfully the LRN LED will display solid green...

Page 4: ...rtly press DIM and LRN button simultaneously to store this value 5 Operating modes The LED Controller supports the following operation modes based on different types of connected devices Mode Default Action Title 24 Compliance Switches only Manual DIM or ON OFF No Occupancy sensors only Auto ON Auto OFF default Auto OFF after 15 minutes No Occupancy sensors and switches Manual DIM or ON Auto OFF C...

Page 5: ...tion for a period defined by OccAutoOffTimer default 15min then light is set to OccAutoOffLevel default 0 Auto OFF function Ramp up SensorRampUpSpeed speed for Auto ON and ramp down SensorRampDownSpeed speed for Auto OFF are configurable default 20 per second Occupancy Sensors and Switches Light can be switched ON OFF manually function as described above Time based automatic switch OFF as defined ...

Page 6: ...meter to 0 will cause all messages to be repeated Note 2 level repeating function and repeating of all messages RepeatLinkedDevicesOnly OFF should only be used if really needed Otherwise the system function can be compromised by collisions of telegrams Status messages The LED controller will transmit a status message EEP D2 40 00 after change of its output state or after StatusMessageTimer has ela...

Page 7: ...y or light level sensor 2 point mode 20 s 0 No ramp immediate Parameter Description Default Notes Rocker Switch Parameters RockerSwitch OnSpeed Ramp up speed when rocker input request light switch ON 20 s 0 No ramp immediate RockerSwitch OffSpeed Ramp down speed when rocker input request light switch OFF 20 s 0 No ramp immediate RockerDim UpSpeed Ramp up speed when rocker input request light dim U...

Page 8: ...usMessage Timer Defines how often status messages are transmitted seconds 0 off 0xFFFF only event based 0xFFFF RepeaterFunction Defines the repeater level of the device OFF 1 Level 2 Level OFF disabled RepeatLinked DevicesOnly Configures the repeater to only repeat telegrams from devices linked to it ON enabled Enable DebugMessages Enable or disable debug messages OFF disabled EnableLink Checker E...

Reviews: