EnOcean LEDD Installation Manual Download Page 4

LED Zone Controller 0-10V Installation Guide  

© 2017 EnOcean GmbH    V2.0 

 

Page  4 

 

Transceiver link / unlink procedure

 

1.

 

Set the other device into linking mode, then shortly press 
the LRN button. The LRN LED starts toggling indicating 
that linking / unlinking mode is active. The connected 
load will toggle between 10% and 90%.  

2.

 

Shortly press the DIM button. This will cause the LED 
Controller to transmit a teach-in message identifying the 
status message EEP used by it. 

3.

 

Shortly press the LRN button again to return to normal 
operation. 

 
Setting the minimum output voltage level 

It is possible to configure the minimum output voltage  
(MinVoltageLevel) of the LED Controller via its button 
interface. This level is typically set to avoid flickering and will 
be the minimum level the load starts at when it is switched 
on. It will not be possible to dim the output below this value.  
Use the following steps to configure this minimum dimming 
value: 
1.

 

Press and hold the DIM button. 
The load will start dimming up and down.  

2.

 

Release the button when the desired minimum output 
voltage (dimming value) is reached. 

3.

 

Shortly press DIM and LRN button simultaneously to 
store this value. 

 

5.

 

Operating modes 

The LED Controller supports the following operation modes 
based on different types of connected devices: 
 

Mode 

Default Action 

Title 24 

Compliance 

Switches only

 

Manual DIM or ON/OFF 

No 

Occupancy 
sensors only

 

Auto ON/ Auto OFF  
(default Auto OFF after 15 minutes) 

No 

Occupancy 
sensors and 
switches

 

Manual DIM or ON, Auto OFF 
Can be configured to Auto ON / 
Auto OFF via remote 
commissioning. (default Auto OFF 
after 15 minutes) 

Yes 

Light level 
sensor

 

Continuous dimming based on 5 
supporting points or two level 
(ON / OFF) dimming 

Yes 

Additional  
central 
controller

 

Dimming via central controller 
overriding sensor and switch input 

Yes 

Additional  
demand 
response 
controller

 

During a demand response event 
output will be reduced to the 
value specified in the command.  
After the demand response 
timeout the system will switch 
back to the previous state. 

Yes 

 

6.

 

Functional behavior 

0-10V Interface 

The minimum output voltage is MinVoltageLevel (default 
1.0V); the maximum output voltage is MaxVoltageLevel 
(default 10.0V).  
Dimming below MinVoltageLevel or above MaxVoltageLevel 
is not possible.  
Level and ramp percentage levels refer to the interval 
between MinVoltageLevel (1%) and MaxVoltageLevel (100%). 
An output level of 0% equals OFF state.  

 

 

 

Summary of Contents for LEDD

Page 1: ...ntrollers n Installs inside or mounts to electrical box using threaded connector n Supports wireless remote commissioning to link devices and set parameters Specifications typ values Power Supply 11 0 V 13 2 V DC Supply Current typ 16 mA 12VDC supply no sourcing 38 mA 12VDC supply 10V 20mA sourcing Power Consumption 200 mW 12 V DC excluding 0 10V sourcing power 460 mW 12 V DC at maximum 0 10V sour...

Page 2: ...enna as shown in figure A 4 Restore power to the circuit 5 Use the setup interface to link devices and configure settings refer to the Linking Configuration sections WARNING Move the module away from any power line before using the local setup interface 3 Device Configuration The LED controller can be configured in two ways n By user input to the local setup interface This approach is used for bas...

Page 3: ...e will stop after 30 seconds if no LRN telegram is received 2 For the transmitter to be linked do one of the following according to the type of device A Sensor click the designated link button B Rocker Pad click the I button top button marked on the switch plastic or I symbol on the back of the switch 3 times quickly 3 If the device has been linked successfully the LRN LED will display solid green...

Page 4: ...rtly press DIM and LRN button simultaneously to store this value 5 Operating modes The LED Controller supports the following operation modes based on different types of connected devices Mode Default Action Title 24 Compliance Switches only Manual DIM or ON OFF No Occupancy sensors only Auto ON Auto OFF default Auto OFF after 15 minutes No Occupancy sensors and switches Manual DIM or ON Auto OFF C...

Page 5: ...tion for a period defined by OccAutoOffTimer default 15min then light is set to OccAutoOffLevel default 0 Auto OFF function Ramp up SensorRampUpSpeed speed for Auto ON and ramp down SensorRampDownSpeed speed for Auto OFF are configurable default 20 per second Occupancy Sensors and Switches Light can be switched ON OFF manually function as described above Time based automatic switch OFF as defined ...

Page 6: ...meter to 0 will cause all messages to be repeated Note 2 level repeating function and repeating of all messages RepeatLinkedDevicesOnly OFF should only be used if really needed Otherwise the system function can be compromised by collisions of telegrams Status messages The LED controller will transmit a status message EEP D2 40 00 after change of its output state or after StatusMessageTimer has ela...

Page 7: ...y or light level sensor 2 point mode 20 s 0 No ramp immediate Parameter Description Default Notes Rocker Switch Parameters RockerSwitch OnSpeed Ramp up speed when rocker input request light switch ON 20 s 0 No ramp immediate RockerSwitch OffSpeed Ramp down speed when rocker input request light switch OFF 20 s 0 No ramp immediate RockerDim UpSpeed Ramp up speed when rocker input request light dim U...

Page 8: ...usMessage Timer Defines how often status messages are transmitted seconds 0 off 0xFFFF only event based 0xFFFF RepeaterFunction Defines the repeater level of the device OFF 1 Level 2 Level OFF disabled RepeatLinked DevicesOnly Configures the repeater to only repeat telegrams from devices linked to it ON enabled Enable DebugMessages Enable or disable debug messages OFF disabled EnableLink Checker E...