LED Zone Controller 0-10V Installation Guide
© 2017 EnOcean GmbH V2.0
Page 4
Transceiver link / unlink procedure
1.
Set the other device into linking mode, then shortly press
the LRN button. The LRN LED starts toggling indicating
that linking / unlinking mode is active. The connected
load will toggle between 10% and 90%.
2.
Shortly press the DIM button. This will cause the LED
Controller to transmit a teach-in message identifying the
status message EEP used by it.
3.
Shortly press the LRN button again to return to normal
operation.
Setting the minimum output voltage level
It is possible to configure the minimum output voltage
(MinVoltageLevel) of the LED Controller via its button
interface. This level is typically set to avoid flickering and will
be the minimum level the load starts at when it is switched
on. It will not be possible to dim the output below this value.
Use the following steps to configure this minimum dimming
value:
1.
Press and hold the DIM button.
The load will start dimming up and down.
2.
Release the button when the desired minimum output
voltage (dimming value) is reached.
3.
Shortly press DIM and LRN button simultaneously to
store this value.
5.
Operating modes
The LED Controller supports the following operation modes
based on different types of connected devices:
Mode
Default Action
Title 24
Compliance
Switches only
Manual DIM or ON/OFF
No
Occupancy
sensors only
Auto ON/ Auto OFF
(default Auto OFF after 15 minutes)
No
Occupancy
sensors and
switches
Manual DIM or ON, Auto OFF
Can be configured to Auto ON /
Auto OFF via remote
commissioning. (default Auto OFF
after 15 minutes)
Yes
Light level
sensor
Continuous dimming based on 5
supporting points or two level
(ON / OFF) dimming
Yes
Additional
central
controller
Dimming via central controller
overriding sensor and switch input
Yes
Additional
demand
response
controller
During a demand response event
output will be reduced to the
value specified in the command.
After the demand response
timeout the system will switch
back to the previous state.
Yes
6.
Functional behavior
0-10V Interface
The minimum output voltage is MinVoltageLevel (default
1.0V); the maximum output voltage is MaxVoltageLevel
(default 10.0V).
Dimming below MinVoltageLevel or above MaxVoltageLevel
is not possible.
Level and ramp percentage levels refer to the interval
between MinVoltageLevel (1%) and MaxVoltageLevel (100%).
An output level of 0% equals OFF state.