LC-Series Controller: 1-4 Channel
ENMET
Manual Revision Date – June 13, 2017
P a g e
|
4
Manual Part No. – 80003-050
3.0 Installation
The
LC-Series Controller
is fully tested prior to delivery. However, it is recommended that the
LC-Series Controller
system be
checked after installation is complete.
CAUTION:
The MCU Control Units and associated modules contain no user serviceable parts. Refer all servicing to qualified
service personnel
The LC series control units
must be mounted in a non-hazardous location
where there is no risk of the presence of potentially
explosive gas
Either a 100-240VAC 50/60 Hz supply or a 24V DC supply can be used to power the control unit
The location of installation should be chosen with regard to the following:
This equipment should not be located near to known sources of heat.
Operating personnel should be within convenient reach of the equipment and within audible distance of alarms
Maximum loop lengths of cable run and cable inductance to resistance ratios must not exceed limits shown in the relevant
loop diagrams
Avoid mounting this equipment near potential sources of electrical interference e.g. motors, switch gear, radio transmitters etc.
Mounting details for the LC Controller enclosures are located below:
LC-2 Control Unit
4.585
[116.4]
2.968
[75.4]
5.937
[150.8]
.38
[9.6]
7.39
[188]
5.26
[134]
6.30
[160.0]
LC-1 CONTROL UNIT
7.656
[194.4]
4.764
[121.0]
9.528
[242.0]
11.02
[280]
6.14
[156]
8.58
[218.0]
.39
[10.0]