ENMET LC-SERIES Operation And Maintenance Manual Download Page 3

LC-Series Controller: 1-4 Channel

 

ENMET 

 

Manual Revision Date – June 13, 2017

 

P a g e

 | 

2

 

Manual Part No. – 80003-050 

 

 

1.0 Introduction 

The LC Series Control Units that provide facilities to monitor a wide variety of industry standard environmental and other sensors. 

 

The LC1 provides 1 monitoring channel. 

 

The LC2 provides up to 2 monitoring channels. 

 

The LC4 provides up to 4 monitoring channels. 

 
The 

LC-Series Controller

 has been designed to allow the use of any ENMET sensor transmitter and has been preprogrammed to 

match the sensor transmitters supplied at time of delivery. The 

LC-Series

 can also be used with any manufactures sensor transmitter 

that can produce a voltage or current output within a specified range; however, it is advisable that you contact ENMET for proper 
setup and programming instructions. Care has been taken with the design of the MCU housings and internal chassis to facilitate ease 
of connection and wire termination.  All on-site wiring to the system is via screw terminal connectors.  The terminal cover has an 
internal label giving details of the external connections.

 

 

N

OTE

:

 

All specifications stated in this manual may change without notice.

 

 

1.1 Unpack 

Unpack the 

LC-Series Controller 

and examine it for shipping damage.  If such damage is observed, notify both 

ENMET

 

customer service personnel and the commercial carrier involved immediately. 

 

Regarding Damaged Shipments 

 

N

OTE

It is your responsibility to follow these instructions.  If they are not followed, the carrier will not honor any claims for 

damage.

 

 

 

This shipment was carefully inspected, verified and properly packaged at 

ENMET

 and delivered to the carrier in good 

condition. 

 

When it was picked up by the carrier at 

ENMET

, it legally became your company’s property. 

 

If your shipment arrives damaged: 

 

Keep the items, packing material, and carton “As Is.”  Within 5 days of receipt, notify the carrier’s local office and 
request immediate inspection of the carton and the contents. 

 

After the inspection and after you have received written acknowledgment of the damage from the carrier, contact 

ENMET

 Customer Service for return authorization and further instructions.  Please have your Purchase Order and Sales 

Order numbers available. 

 

ENMET

 either repairs or replaces damaged equipment and invoices the carrier to the extent of the liability coverage, usually 

$100.00.  Repair or replacement charges above that value are your company’s responsibility. 

 

The shipping company may offer optional insurance coverage. 

ENMET

 only insures shipments with the shipping company 

when asked to do so in writing by our customer.  If you need your shipments insured, please forward a written request to 

ENMET

 Customer Service. 

 

Regarding Shortages 

If there are any shortages or questions regarding this shipment, please notify 

ENMET

 Customer Service within 5 days of receipt at 

the following address: 

ENMET 

680 Fairfield Court 

Ann Arbor, MI 48108 

734-761-1270 Fax 734-761-3220 

Toll Free: 800-521-2978 

1.2 Check Order 

Check, the contents of the shipment against the purchase order.  Verify that the 

LC-Series Controller 

is received as ordered.  If 

there are accessories on the order, ascertain that they are present.  Check the contents of calibration kits.  Notify 

ENMET

 customer 

service personnel of any discrepancy immediately. 
 

1.3 Serial Numbers  

Each 

LC-Series Controller 

is serialized.  These numbers are on tags on the equipment and are on record in an 

ENMET

 database. 

 

 

Summary of Contents for LC-SERIES

Page 1: ...ENMET 680 Fairfield Court Ann Arbor MI 48108 734 761 1270 Fax 734 761 3220 www enmet com LC Series Controller 1 4 Channel Operation and Maintenance Manual...

Page 2: ...ler Module 12 5 2 Analogue Output Configuration 14 5 2 1 4 20mA Current Source 14 5 2 2 4 20mA Current Sink 15 5 2 3 1 5V Voltage Output 16 6 0 MAINTENANCE 17 7 0 TECHNICAL DATA AND SPECIFICATIONS 18...

Page 3: ...ET and delivered to the carrier in good condition When it was picked up by the carrier at ENMET it legally became your company s property If your shipment arrives damaged Keep the items packing materi...

Page 4: ...er most indication of Fault Condition Keypad Buttons 4 2 as indicated in figure 1 that are used during normal operation and 2 that are used during setup and programming Menu Main Select Switch Increas...

Page 5: ...V DC supply can be used to power the control unit The location of installation should be chosen with regard to the following This equipment should not be located near to known sources of heat Operatin...

Page 6: ...LC Series Controller 1 4 Channel ENMET Manual Revision Date June 13 2017 P a g e 5 Manual Part No 80003 050 LC 4 Control Unit Figure 2 Mounting LC Series...

Page 7: ...ly would suffice AC Mains Connection The power supply board has three screw terminals connector assigned for the connection of an AC supply Pin 1 Earth Pin 2 Live input Pin 3 Neutral input Recommendat...

Page 8: ...ny modifications regardless of the type and quantity of detector heads being used TRACO POWER FG AC N AC L Input 100 240 VAC 47 63 Hz 0 375 A max Output 24VDC 625 mA TML 15124 Fault relay Fuse 1 Fuse...

Page 9: ...3 Hz 0 375 A max Output 24VDC 625 mA T ML 15124 Display PCB Connector E L N 24V 0V 15 16 17 18 OUTPUT 4 20 mA SOUNDER SOUNDER J1 J2 J3 J4 J5 J6 J7 J8 J9 J10 J11 J12 J13 J14 D5 D4 100 240 VAC D C FLT L...

Page 10: ...13 14 J1 J2 J3 J4 J5 J6 J7 J8 J9 FS1 FS2 SW1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Power supply sectionI O interface section Channel Note connections 12 13 may not be fitted o...

Page 11: ...s Pin 13 Signal In 1 5 Vdc Pin 14 Signal In 4 20mA Pin 15 Voltage Out to S T Pin 16 Ground to S T Chanel 2 Pins 25 to 36 The same functions as 13 to 24 Chanel 3 Pins 37 to 48 The same functions as 13...

Page 12: ...ment e g cranes doors etc Install all cables neatly and securely Detectors for gases that are lighter than air should be positioned at or below a high level Detectors for gases that are heavier than a...

Page 13: ...alarm level 3 Yellow LED indication of fault condition An Audible signal is also provided by a sounder mounted within Microcontroller module This provides a local audible tone during alarm or conditi...

Page 14: ...thers OFF J1 J2 J3 J4 J5 J6 J7 J8 J9 Connect the wires from the detector head to connector on the input module observing the following Detector Head Label 4 20mA Loop Channel 1 Pin Number Channel 2 Pi...

Page 15: ...librated if in use refer to MCU Software Configuration and System Calibration Manual 5 2 1 4 20mA Current Source Chart record er 0V Alarm level1 J1 J2 J3 J4 J5 J6 J7 J8 J9 J10 J11 J12 J13 J14 Alarm le...

Page 16: ...1 26 27 28 29 30 31 32 33 34 35 36 Channel 2 38 39 40 41 42 43 44 45 46 47 48 Channel 3 50 51 52 53 54 55 56 57 58 59 60 Channel 4 16 17 18 LC 1 15 13 25 37 49 19 20 The Input Module can also sink cur...

Page 17: ...41 42 43 44 45 46 47 48 Channel 3 50 51 52 53 54 55 56 57 58 59 60 Channel 4 16 17 18 LC 1 15 13 25 37 49 19 20 Chart recorder ve ve The LC Control Unit can provide a voltage output i e zero gas 1V f...

Page 18: ...has occurred Clean control unit casing using a clean cloth Clean detector heads using a clean DAMP cloth NOTE Use of a dry cloth would constitute a static hazard Inspect detector heads and ensure the...

Page 19: ...cates power ON LED Indications Option 2 Red Red Yellow Indicates alarm level 1 condition Indicates alarm level 2 condition Indicates fault condition Input Modules Number of channels 1 max Signal Input...

Page 20: ...dicates alarm level 3 condition Indicates alarm level 2 condition Indicates alarm level 1 condition Indicates fault condition Input Modules Number of channels 2 max Signal Inputs x 2 4 20mA Current Lo...

Page 21: ...d Red Red Yellow Indicates power ON Indicates alarm level 3 condition Indicates alarm level 2 condition Indicates alarm level 1 condition Indicates fault condition Input Modules Number of channels 4 m...

Page 22: ...the inspection by the Seller confirms that the product is defective it will be repaired or replaced at no charge within the stated limitations and returned prepaid to any location in the United State...

Page 23: ...the Service Request Form assists in the expedient service and return of your unit and failure to provide this information can result in processing delays ENMET charges a one hour minimum billing for...

Page 24: ...it Appears on Card RETURN SHIPPING METHOD UPS Ground UPS 3 Day Select UPS Next Day Air UPS ND Air Saver UPS 2 Day Air UPS Account FedEx Ground FedEx Air Express Saver FedEx Air Overnight Std FedEx Air...

Reviews: