LC-Series Controller: 1-4 Channel
ENMET
Manual Revision Date – June 13, 2017
P a g e
|
13
Manual Part No. – 80003-050
Connection Procedure
Disconnect power from the system.
Remove the terminal cover to gain access to the wiring.
Remove the terminal cover and display module to gain access to the configuration link settings.
Configure the jumper switches as shown below (i.e. J1, J2, J4, J5, J8 and J9 switched ON, all others OFF)
J
1
J
2
J
3
J
4
J
5
J
6
J
7
J
8
J
9
Connect the wires from the detector head to connector on the input module observing the following:
Detector Head Label
4-20mA Loop
Channel 1
Pin Number
Channel 2
Pin Number
Channel 3
Pin Number
Channel 4
Pin Number
–
14
26
38
50
+
15
27
39
51
Connect power to the system and ensure the detector head operates (text on LCD display, LED will flash once every six
seconds approximately).
Perform software configuration (refer to ‘LC Software Configuration and System Calibration Manual’).
Perform system calibration (refer to ‘LC Software Configuration and System Calibration Manual’).