35
E
10W230WIFI(
E
10B230WIFI) - FULL MANUAL
8.4.5 Sensor Selection
8.4.5.1 Internal temperature sensor (IN)
By default, the thermostat measures the temperature with the thermostat’s internal built-in temperature sensor.
PLEASE NOTE!
For the selected option with an internal sensor, if an additional floor sensor is connected to the terminals S1-S2 of the thermostat, both sensors are active
(internal and external). The internal sensor measures and controls the temperature in the room, and the additional sensor acts as a floor protection
against overheating and overcooling. The factory setting for overheat protection is 26°C, adjustable from 10°C to 45°C. When this value is exceeded, the
thermostat will turn off the heating. When overheating occurs, the floor protection icon will flash on the thermostat’s LCD display. The app also shows the
message „Heating off - sensor overheating”. After the floor sensor has cooled down, the heating restarts. The factory temperature setting for protection
against floor overcooling is fixed at 5°C. After the temperature on the floor sensor drops below 5°C, the thermostat will automatically start heating.
The Floor Protection icon will flash on the thermostat LCD. The app will display the message „Heating on - FROST mode”.
Select „Settings”.
Additionally, you can set the maximum set
temperature (from 10°C to 45°C) for the
floor sensor (if there is an underfloor
heating system and the sensor is connected).
Select internal (IN) sensor.
1
4
2
5
3
Enter the thermostat interface.
Use the slider to set the IN sensor
deadzone value
from ± 0.1°C to ± 0.5°C.
3