A
PD MANUAL
IOM-39
21 of 36
Aug 99 R1
6.
solenoid
drop,
or
7.
single
pumpdown,
or
8.
recycling
pumpdown,
depending
on
the
specific
application.
9.
Hot
Gas
Bypass
(Optional):
Hot
gas
bypass
is
provided
on
systems
to
prevent
frost
formation
on
the
evaporator
coil
during
low
load
conditions.
The
hot
gas
valve
will
start
to
open
at
a
pressure
that
corresponds
to
approximately
34°F
(1°C)
coil
temperature.
All
compressors
equipped
with
unloading
should
be
fully
unloaded
before
hot
gas
starts
to
open.
10.
Cylinder
Unloading
(Optional)
This
is
a
form
of
capacity
control
on
some
compressors
that
reduces
the
pumping
capacity
of
the
compressor
during
low
load
conditions.
Unloading
may
be
activated
by
the
control
system
or
by
a
pressure
actuated
Cylinder
Unloading
Control
(CUC).
11.
Water
Cooled
Systems
(Optional)
If
the
system
is
equipped
with
a
water
cooled
condenser,
set
the
water
flow
valve
to
maintain
a
saturated
discharge
temperature
of
approximately
105°F
to
115°F
(40°C
to
46°C).
This
applies
both
to
cooling
tower
systems
and
city
water
systems.
Typical
water
valve
pressure
setting:
R134a
=
150
psig
(1040
kPa)
R407C
=
270
psig
(1870
kPa)
R410A
=
370
psig
(2550
kPa)
Caution:
When
recovering
refrigerant
from
a
system
equipped
with
a
water
cooled
condenser,
the
water
valve
must
be
manually
opened
so
water
flows
continuously
through
the
condenser
while
the
refrigerant
is
being
recovered.
Failure
to
do
so
can
cause
the
condenser
to
freeze,
which
will
permanently
damage
the
condenser.
REFRIGERANT
HANDLING
Recovery,
reuse,
recycling,
reclamation,
and
safe
disposal
of
refrigerant
is
the
only
acceptable
practice
today.
Venting
of
refrigerant
into
the
atmosphere
during
installation
or
servicing
is
unacceptable.
To
avoid
damage,
use
an
accepted
refrigerant
recovery
system
whenever
removing
refrigerant.
When
working
with
refrigerants
you
must
comply
with
all
local
government
safety
and
environmental
laws.
Caution:
Environmental
laws
govern
the
safe
handling
of
refrigerants.
Only
personnel
qualified
to
safely
handle
refrigerant
may
service
this
equipment.
All
refrigerant
must
be
handled
safely
and
responsibly.
Records
must
be
kept
as
required
by
the
authorities
having
jurisdiction.
When
servicing
the
refrigeration
system,
the
refrigerant
must
be
properly
recovered
to
prevent
release
to
atmosphere.
Always
use
the
same
refrigerant
as
indicated
on
the
unit
rating
plate.