195
Installation instructions for professionals
TROUBLESHOOTING
Alarm
Reason
Instruction
Solution
LTO input
village
(TE-05 min)
Heat exchanger trace has
broken
A green trace circles the heat exchanger.
Check if the trace can be seen from the LTO
cell review hole. If it cannot be seen, the trace
has broken.
Change the trace
The heat exchanger trace is
lubricated so that it can slide
A green trace circles the heat exchanger.
Check from the LTO trace review hole if the
pulley is rotating even though the LTO cell is
not rotating.
Change the trace
Exhaust blower has stopped
Open the access door while the machine
is operating. The supply blower should be
rotating. In LTR model machines, press with a
screwdriver and check, if the blower starts.
Change blowers
Exhaust air filter is blocked
Open the access door when the machine is
off. Pull out the filter and check the dirtiness
of the filter.
Change the exhaust filter
Exhaust air valves adjusted
wrong
Contact the company that installed the
ventilation unit and find out if the air flow and
valves are correctly adjusted.
Contact the maintenance.
Ducts have inadequate
insulation
Check the thickness of insulation in supply
and exhaust ducts, and add insulation if
necessary.
Contact the maintenance.
The protection against
additional heating
overheating has launched.
Find out the cause for the failure and reset the
protection against overheating (® button in
the radiator).
Contact the maintenance.
The motor/gearbox in the
heat exchanger is faulty
Open the access door while the machine is
operating and listen, if the sound comes from
the LTO.
Contact the maintenance.
The LTO controller card is
faulty (EDA models)
The LTO cell is controlled by a separate
controller card that is located in the electric
box of the machine.
Contact the maintenance.
LTO pulley has separated
from the shaft
Check from LTO trace review hole if the shaft is
rotating empty and the pulley is in its place.
Tighten the screw on the pulley.
Contact the maintenance.
Summary of Contents for Pelican eAir
Page 8: ...8 Kanavaliitännät ulkoilma poistoilma jäteilma tuloilma ...
Page 20: ...20 13 15 11 14 Lisävaruste 1 2 min 12 9 10 ...
Page 49: ...49 Ammattilaisen asennusohje ...
Page 52: ...52 Pelican eAir Installationsanvisningar för ventilationsaggregat Svenska ...
Page 58: ...58 Kanalanslutningar uteluft frånluft avluft tilluft ...
Page 70: ...70 13 15 11 14 Extra tillbehör 1 2 min 12 9 10 ...
Page 99: ...99 Installationsanvisningar för yrkesfolk ...
Page 102: ...102 Installeringsinstruksjoner for ventilasjonsenheten Norsk Pelican eAir ...
Page 108: ...108 Kanalanslutningar uteluft avtrekksluft avkastluft tilluft ...
Page 120: ...120 13 15 11 14 Ekstrautstyr 1 2 min 12 9 10 ...
Page 149: ...149 Installasjonsinstrukser for fagfolk ...
Page 152: ...152 Pelican eAir Installation instructions for the ventilation unit English ...
Page 158: ...158 Duct connections outdoor air extract air exhaust air supply air ...
Page 170: ...170 13 15 11 14 Extra 1 2 min 12 9 10 ...
Page 199: ...199 Installation instructions for professionals ...
Page 205: ...205 ...
Page 206: ...206 Enervent Zehnder Oy Kipinätie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com ...
Page 207: ...207 ...
Page 211: ...211 Enervent Zehnder Oy Kipinätie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com ...
Page 220: ...220 eAir CG liitännät eAir CG anslutningar eAir CG koblinger eAir CG connections ...
Page 223: ...223 ...