![enervent Pelican eAir Installation Instructions Manual Download Page 187](http://html1.mh-extra.com/html/enervent/pelican-eair/pelican-eair_installation-instructions-manual_2411677187.webp)
187
Installation instructions for professionals
8
Defrost
OFF
Options are ON/OFF. The function is active during
winter season, if enabled. When defrosting is active,
the supply air fan stops and the extract air fan runs
at a set speed.
Limit temperature
for winter boost
8°C
When the outside temperature is below this value,
the heat recovery is always on 100%.
Arctic mode
OFF
Options are ON/OFF. Arctic mode is a defrost-
ing mode that takes the outside air temperature
and the absolute humidity of the extract air into
account when determining the need for defrosting.
Operating modes
9
Supply air
30 %
This value defines the supply air fan speed in Home
operating mode.
Extract air
30%
This value defines the extract air fan speed in Home
operating mode.
10
Summer night
cooling
OFF
Options are ON/OFF. Summer night cooling boosts
the fan speed to increase cooling when the outside
air is cooler than the room air.
Start temperature
25°C
Summer night cooling starts when the tempera-
ture of extract air exceeds this temperature value.
Stop temperature
21°C
Summer night cooling stops when the temperature
of extract air drops below this temperature value.
Lowest outside
temperature
10°C
The temperature of outside air must be higher than
this value for the summer night cooling to start.
Min. temperature
difference
1°C
Outside air must be cooler than extract air by this
value.
Supply air
70 %
The speed of the supply air fan when summer
night cooling is active.
Extract air
70 %
The speed of the extract air fan when summer
night cooling is active.
Start time
22.00
Summer night cooling is only allowed after this
specified time.
Summary of Contents for Pelican eAir
Page 8: ...8 Kanavaliitännät ulkoilma poistoilma jäteilma tuloilma ...
Page 20: ...20 13 15 11 14 Lisävaruste 1 2 min 12 9 10 ...
Page 49: ...49 Ammattilaisen asennusohje ...
Page 52: ...52 Pelican eAir Installationsanvisningar för ventilationsaggregat Svenska ...
Page 58: ...58 Kanalanslutningar uteluft frånluft avluft tilluft ...
Page 70: ...70 13 15 11 14 Extra tillbehör 1 2 min 12 9 10 ...
Page 99: ...99 Installationsanvisningar för yrkesfolk ...
Page 102: ...102 Installeringsinstruksjoner for ventilasjonsenheten Norsk Pelican eAir ...
Page 108: ...108 Kanalanslutningar uteluft avtrekksluft avkastluft tilluft ...
Page 120: ...120 13 15 11 14 Ekstrautstyr 1 2 min 12 9 10 ...
Page 149: ...149 Installasjonsinstrukser for fagfolk ...
Page 152: ...152 Pelican eAir Installation instructions for the ventilation unit English ...
Page 158: ...158 Duct connections outdoor air extract air exhaust air supply air ...
Page 170: ...170 13 15 11 14 Extra 1 2 min 12 9 10 ...
Page 199: ...199 Installation instructions for professionals ...
Page 205: ...205 ...
Page 206: ...206 Enervent Zehnder Oy Kipinätie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com ...
Page 207: ...207 ...
Page 211: ...211 Enervent Zehnder Oy Kipinätie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com ...
Page 220: ...220 eAir CG liitännät eAir CG anslutningar eAir CG koblinger eAir CG connections ...
Page 223: ...223 ...