109
Installation instructions for professionals
Problem
Reason
Help
Solution
AL2
Supply air is cold
after the rotary heat
exchanger�
The heat exchanger belt has broken�
The heat exchanger has a
green belt� Check the heat
exchanger rotor from the belt's
control hole� If the belt is not
visible, it is broken�
Change the belt�
The heat exchanger belt-wheel is oily
and the belt is slipping
The heat exchanger has a
green belt� Check the heat
exchangers rotor from the
belt's control hole if the belt
wheel is rotating even if the
heat exchanger rotor is not
rotating�
Change the belt�
Error in the heat exchanger motor/
gearbox
Open the service hatch while
the unit is on and listen if the
noise is coming from the heat
exchanger�
Contact a service representive�
AL3
Supply air is cold
The exhaust fan has stopped�
Open the service hatch when
the unit is running� The exhaust
fan needs to be on� With the
LTR unit you must push down
the door coupling with a
screwdriver and check if the
unit starts�
Change the fans�
The exhaust filter is clogged�
Open the service hatch when
the unit is not on� Remove the
filters and check if they are
dirty�
Change the supply air filter�
The ventilation unit runs with a too
low fan speed�
The correct fan speed was
chosen when the ventilation
was balanced in your house�
Check your ventilation
installation sheet for the
correct fan speeds�
Adjust the fan speed from the control panel�
Contact a service representive�
The ventilation is adjusted incorrectly�
Contact the company that has installed your
ventilation unit and check if the houses
airflow/valves has been adjusted correctly�
Contact a service representive�
AL4
Supply fan malfunction
The supply air fan has stopped
Open the service hatch when
the unit is running� The exhaust
fan needs to be on� With the
LTR unit you must push down
the door coupling with a
screwdriver and check if the
unit starts�
Contact a service representive�
AL5
Extract fan malfunction
The exhaust fan has stopped�
Open the service hatch when
the unit is running� The exhaust
fan needs to be on� With the
LTR unit you must push down
the door coupling with a
screwdriver and check if the
unit starts�
Change the fans�
Contact a service representive�
Summary of Contents for eWind Pegasos
Page 8: ...8 Kanavaliitännät ulkoilma poistoilma jäteilma tuloilma ...
Page 13: ...13 Ammattilaisen asennusohje 9 10 12 11 Wifi moduulin asennus 1 2 A B A 3 4 ...
Page 27: ...27 Ammattilaisen asennusohje ...
Page 28: ...28 ...
Page 30: ...30 Installationsanvisningar för ventilationsaggregat Svenska Pegasos eWind Pegasos XL eWind ...
Page 36: ...36 Kanalanslutningar tilluft uteluft frånluft avluft ...
Page 55: ...55 Installationsanvisningar för yrkesfolk ...
Page 56: ...56 ...
Page 58: ...58 Installeringsinstruksjoner for ventilasjonsenheten Norsk Pegasos eWind Pegasos XL eWind ...
Page 64: ...64 Kanalkoblinger uteluft avtrekksluft avkastluft tilluft ...
Page 69: ...69 Installasjonsinstrukser for fagfolk Installasjon av Wifi modulen 1 2 A B A 3 4 9 10 12 11 ...
Page 83: ...83 Installasjonsinstrukser for fagfolk ...
Page 84: ...84 ...
Page 86: ...86 Installation instructions for the ventilation unit English Pegasos eWind Pegasos XL eWind ...
Page 92: ...92 Duct connections outdoor air extract air exhaust air supply air ...
Page 111: ...111 Installation instructions for professionals ...
Page 112: ...112 ...
Page 130: ...130 eWind CG liitännät eWind CG anslutningar eWind CG koblinger eWind CG connections ...
Page 131: ...131 Installation instructions for professionals ...
Page 134: ......
Page 135: ......