background image

1164-EnertexKNXIPSecureRouter_US-2.odt, 2019-03-25                                             

Seite 8 von 19 

Use a static address 

The user specifies the IP settings.

Comissioning Password 

A password from which the ETS generates a key. This is the key to 

secure commissioning (see above).

Authentication Code 

With the authentication password, the user proves that he has access to 

the project.

MAC Address 

Is a device property

Multicast Address 

Is given by the backbone configuration (see Figure 1)

Device-specific parameters

General

Figure 4: General settings of the device

Name

Options

Description

(Text)

The ETS has manufacturer-
independent uniform parameter 

dialogs for various settings. To 
simplify the application, a note text is 

displayed here.

Enable Special Functions

off/on

Enertex® devices offer special 
functions to ensure a maximum of 

flexibility.

Special Functions

Behavior of the KNX side

Enertex

®

 Bayern GmbH – Ebermannstädter Straße 8 - 91301 Forchheim - Deutschland - [email protected]

Summary of Contents for Enertex KNX IP Secure Router

Page 1: ...Manual and Configuration Enertex KNX IP Secure Router Enertex Bayern GmbH Ebermannst dter Stra e 8 91301 Forchheim Deutschland mail enertex de...

Page 2: ...t claim to be complete or correct Inhalt Security Notes 3 Assembly and connection 3 Comissioning 3 Boot 3 Displays 3 Reset 4 Functional Overview 4 ETS Parameter 4 Terms 4 ETS 5 6 6 and ETS 5 7 0 5 Ver...

Page 3: ...short time At the end of the boot process the IP address of the device is shown in the display If the IP address assignment is done via DHCP server the boot time is extended accordingly As soon as KN...

Page 4: ...communication and programming mode Power indicator OLED display for status messages parameter displays etc Special functions Configuration via ETS and Telnet SNTP server Measurement of the TP bus volt...

Page 5: ...A simple TCP server on port 23 that enables direct text based communication with the IP device Telnet is a de facto standard used at the window level e g with Putty is addressed Secure Mode If the dev...

Page 6: ...his click on Topology directly above Dynamic Folders see Figure 1 you will find the settings for the Multicast of the Backbone Network latency see Figure 1 can be changed if the routing is over a larg...

Page 7: ...all parameters are then transmitted in encrypted form although e g Tunnel connections are still unencrypted Secure Tunnelling If activated the tunnel connections can only be established via KNX Secure...

Page 8: ...property Multicast Address Is given by the backbone configuration see Figure 1 Device specific parameters General Figure 4 General settings of the device Name Options Description Text The ETS has man...

Page 9: ...hibit programming from TP side off on See parameter dialog Max number of telegrams to KNX TP 5 50 See parameter dialog Standard tunnel preferred IP Enertex devices offer the possibility for standard t...

Page 10: ...controlled by default with a connection timeout of 1 second This may be too short for connections over the Internet UDP Connection Timeout 1 0 8 0 sec Tunnel X should preferably be used for communicat...

Page 11: ...scription Physically addressed filter block route The physically addressed telegrams e g actuator programming may be routed blocked or filtered via the routing This affects all communication related t...

Page 12: ...ng Groups 14 and 15 are grouped together to form a block Main Group 16 to 31 filter block route Group telegrams can be routed blocked or filtered via the routing The groups 16 and 31 are here combined...

Page 13: ...or filtered via the routing With this function the parameter dialog can be opened for this purpose Extended Group Address Filter For both directions in addition to the block oriented filtering of grou...

Page 14: ...inactive filter block forward Group telegrams of this main group can be routed blocked or filtered via the routing If the filter is not active the behavior of the parameters of Figure 8 and Figure 9...

Page 15: ...mask 255 255 255 0 tpconfig Show KNX parameters KNX bus state up KNX address 15 15 000 Serial number 00 a6 00 00 00 01 tpconfig help set Set KNX parameters via the telnet interface Set the TP address...

Page 16: ...KNX Number of telegrams that could not be sent to the KNX bus TX tunnel re req Number of telegrams that had to be repeated in the tunnel connections TP bus voltage Current bus voltage at the time of...

Page 17: ...unaddr setall tunaddr help KNX address of a tunnel read tunaddr or change e g tunaddr 1 15 15 240 set all tunnel addresses consecutively from a certain start address tunaddr setall 15 15 15 or reset t...

Page 18: ...programming the secure mode this is a security risk factory_reset Reset to factory settings and reboot die Test hardware watchdog Executes reset reboot reboot logout end Telnet Session Latest document...

Page 19: ...r 2 Redistributions in binary form must reproduce the above copyright notice this list of conditions and the following disclaimer in the documentation and or other materials provided with the distribu...

Reviews: