
49
IOM, ZS/ZT Models
Enertech Global
Specifications are subject to change without notice (03.09.2014)
7
RSBS2332A2V22C24SM28, RSBS2325A2V22C17SM29
1 For a 50Hz supply, minimum interruption detection is of 50ms (+20ms/
-
0ms).
2 Orange LED will be ON if the time between starts and/or time from stop to start has not elapsed.
Following the recovery between starts and/or from stop to start, if control voltage is present, the RSBS shall try to restart the compressor.
Mode of Operation (Voltage Interruptions)
Mains operationalvoltage
230VAC
0VAC
Green LED
Control Voltage
20ms*
Controller output
Recovery indication, orange LED
Alarm relay contact
> 600ms
On *
50ms
1
3
On
2
Mains operational voltage
M
230VAC
2
0VAC
0
< 300ms *
Green LED
G
Control Voltage
C
20ms*
2
Controller output
C
Alarm indication, Red LED
A
Alarm relay contact
A
Alarm recovery
F
On
Flashing
*
<300 ms
50ms
1
Mode of Operation (Voltage Dips)
SECTION 8: SOFT START CONTROLS