background image

4

Cell strings connected in parallel

Using constant voltage chargers and ensuring that the

connections made between the charger and the batteries have

the same electrical resistance, no special arrangements have to

be made for batteries in parallel.

Although no special circuit arrangements are required, where the

parallel connection is made at the charger or distribution board, to

avoid out of step conditions, the bus bar run length and the area of

cross section should be designed so that the circuit resistance

value for each of the strings is equal within limits ± 5%.

Charging

Float voltage

The recommended float charge voltage is 2.28 volts per cell at

20°C.

Following a commission charge and after 6 months continuous

charge at the recommended float voltage, individual cell voltages

will stabilise within ±4.5% of the mean applied voltage. 

However, immediately following commissioning and for the initial 6

months of continuous float charge, individual cell voltage values

outside the above tolerance may be observed without adverse

effect. There is no relationship between a cell’s float voltage and

its discharge capacity. Cells are perfectly capable of giving their

discharge capacity even when outside the ±4.5% range.

After 6 months service, should any individual cell or monobloc

show a continuing reduction or increase in voltage outside the

above limits over 3 successive monthly periods, Enersys should be

contacted for advice.

When the average ambient temperature deviates more than ±5ºC

from the reference temperature (20°C), it is necessary to adjust

the float voltage as follows:

Temperature

Float voltage range per cell

0°C

2.33-2.36V

10°C

2.30-2.33V

20°C

2.27-2.30V

25°C

2.25-2.28V

30°C

2.24-2.27V

35°C

2.22-2.25V

40°C

2.21-2.24V

45°C

2.19-2.22V

50°C

2.18-2.21V

If the charger does not permit an adjustment of float voltage in

relation to the temperature, it is possible to set a float voltage

value according to the temperature ranges as indicated in the last

table of this publication.

Charging current

A discharged VRLA battery will accept a high recharge current,

but for those seeking a more economical charging system a

current limit of 0.08 C

10

or 0.1 C

3

(A) is adequate.

Fast recharge

Increasing the charge voltage to 2.40Vpc with a current limited to

0.1 C

10

or 0.125 C

3

(A) can reduce recharge times. Fast charge

should be stopped after approximately 10 to 15 hours. In order to

achieve a normal service life, this charge regime must not be used

more than once per month. 

Float charge ripple

Excessive ripple on the D.C. supply across a battery has the effect

of reducing life and performance.

It is therefore recommended that voltage regulation across the

system, including the load but without the battery connected,

under steady state conditions, shall be better than ±1% between

5% and 100% load.

State of charge

The battery state of charge can be determined approximately by

measuring the open circuit voltage after the battery has been at

rest for a minimum of 24 hours at 20°C.

Voltage

State of charge

2.14Vpc

100%

2.10Vpc

80%

2.07Vpc

60%

2.04Vpc

40%

2.00Vpc

20%

Open circuit voltage variation with temperature is 2.5mV per 10°C.

Discharging

PowerSafe VX batteries must not be left in a discharged condition

after supplying the load but must immediately be returned to float

recharge mode.

Failure to observe these conditions may result in greatly reduced

service life.

Publication No: EN-VX-IOM-001  February 03

www.enersysinc.com

Summary of Contents for PowerSafe VX

Page 1: ...Installation Operations and Maintenance Instructions Publication No EN VX IOM 001 February 03...

Page 2: ...unpack the monoblocs and accessories before commencing assembly and erection and not to unpack and erect monobloc by monobloc All monobloc units should be handled carefully as the plastic container c...

Page 3: ...eration gas recombination efficiency 95 Batteries must be installed in accordance with national standards for instance EN 50272 2 otherwise in accordance with the manufacturer s instructions Please no...

Page 4: ...per cell 0 C 2 33 2 36V 10 C 2 30 2 33V 20 C 2 27 2 30V 25 C 2 25 2 28V 30 C 2 24 2 27V 35 C 2 22 2 25V 40 C 2 21 2 24V 45 C 2 19 2 22V 50 C 2 18 2 21V If the charger does not permit an adjustment of...

Page 5: ...g must be carried out with a damp cotton cloth only Check monthly that total voltage at battery terminals is N x 2 28 V for a temperature at 20 C N the number of cells in the battery Take annual readi...

Page 6: ...ical specifications of bloc All dimensions in millimetres Item No Description Cat No 1 Fastener set M6 2 Inter unit connector SUB5176 3 Inter tier connector 35 mm2 max 4 Insulating terminal cover SPH0...

Page 7: ...28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94...

Page 8: ...ters P O Box 14145 Reading PA 196212 4145 USA Tel 1 610 208 1991 1 800 538 3627 Fax 1 610 372 8613 EnerSys EMEA Houtweg 26 1140 Brussels Belgium Tel 32 0 2 247 94 47 Fax 32 0 2 247 94 49 EnerSys Asia...

Reviews: