3

A rigid plastic insulating cover is provided which protects the unit

terminals. These are factory fitted and there is no need to remove

them until access to the terminals is required. 

Storage

Store the batteries in a dry, clean and preferably cool location.

As the batteries are supplied charged it is advised not to store

batteries without a refreshing charge for more than:

6 months at 20°C

3 months at 30°C

6 weeks at 40°C

3 weeks at 50°C 

The refreshing charge needs to be at 2.27-2.30Vpc at 20°C for 48 to

96 hours. A current limit is not essential, but for optimum charge

efficiency the current output of the charger can be limited to 10%

of the 3 hour capacity rating. The need for a refreshing charge

can also be determined by measuring the open circuit voltage of

the stored battery. Refreshing charge is advised if the voltage

drops below 2.10Vpc. Failure to observe these conditions may

result in greatly reduced capacity and service life.

Temperature

Avoid placing the battery in a hot environment or in front of a

window. The battery will give the best performance and service

life when working at a temperature between 20°C and 25°C.

Operating temperatures should not 45°C or fall below -

30°C.

Ventilation

Under normal conditions gas release is very low and natural

ventilation is sufficient for cooling purposes and inadvertent

overcharge, enabling PowerSafe VX batteries to be used safely in

offices and with main equipment.

However care must be taken to ensure adequate ventilation when

placed in cabinets. Batteries must not be placed in sealed

cabinets.

Installation

Install batteries in a clean and dry area. PowerSafe VX products

release minimal amounts of gas during normal operation (gas

recombination efficiency 

95%). Batteries must be installed in

accordance with national standards 

(for instance EN 50272-2), otherwise in accordance with the

manufacturer’s instructions.

Please note that each monobloc is supplied complete with a

fastener set, i.e. nut, spring washer and plain washer. These are

fitted to the threaded stud of each terminal pillar prior to despatch

from the factory.

Enersys battery racks or cabinets are recommended when

installing the monoblocs. Assemble the rack according to

instructions. Place the battery blocs on the rack at their correct

cell centres (as indicated on the connection drawing) and arrange

the positive and the negative terminals for connection according

to the wiring diagram. 

Connection of monoblocs

When all monoblocs have been placed on the stands/in the

cabinets, connect them together by means of the connecting straps

and fastener set, in sequence, pillar, connecting strap, plain washer,

spring washer and nut.

Tighten the fastener set nut(s) to a level of fastening torque of 5 ±0.5

Nm. Never use a standard spanner, use insulated tools only.

A loose connector can cause problems in charger adjustment,

erratic battery performance, possible damage to the battery

and/or personal injury.

Single solid sleeved copper strap connector type SUB5176 is used to

connect units located on the same tier of the stand (or on the same

shelf of a cabinet). A single flexible insulated cable connector is

used for inter-tier (or inter-shelf) connection which is provided when

the stand is supplied by Enersys.

Putting the terminal cover back

Insulating terminal covers have been designed to be fitted on

completion of the connecting up sequence of the battery. Where

inter-tier flexible insulated cable connectors are used, it will be

necessary to remove the corner of the cover by simply snapping it

off.

Publication No: EN-VX-IOM-001  February 03

www.enersysinc.com

Summary of Contents for PowerSafe VX

Page 1: ...Installation Operations and Maintenance Instructions Publication No EN VX IOM 001 February 03...

Page 2: ...unpack the monoblocs and accessories before commencing assembly and erection and not to unpack and erect monobloc by monobloc All monobloc units should be handled carefully as the plastic container c...

Page 3: ...eration gas recombination efficiency 95 Batteries must be installed in accordance with national standards for instance EN 50272 2 otherwise in accordance with the manufacturer s instructions Please no...

Page 4: ...per cell 0 C 2 33 2 36V 10 C 2 30 2 33V 20 C 2 27 2 30V 25 C 2 25 2 28V 30 C 2 24 2 27V 35 C 2 22 2 25V 40 C 2 21 2 24V 45 C 2 19 2 22V 50 C 2 18 2 21V If the charger does not permit an adjustment of...

Page 5: ...g must be carried out with a damp cotton cloth only Check monthly that total voltage at battery terminals is N x 2 28 V for a temperature at 20 C N the number of cells in the battery Take annual readi...

Page 6: ...ical specifications of bloc All dimensions in millimetres Item No Description Cat No 1 Fastener set M6 2 Inter unit connector SUB5176 3 Inter tier connector 35 mm2 max 4 Insulating terminal cover SPH0...

Page 7: ...28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94...

Page 8: ...ters P O Box 14145 Reading PA 196212 4145 USA Tel 1 610 208 1991 1 800 538 3627 Fax 1 610 372 8613 EnerSys EMEA Houtweg 26 1140 Brussels Belgium Tel 32 0 2 247 94 47 Fax 32 0 2 247 94 49 EnerSys Asia...

Reviews: