13
9400016-J0 Rev E
CXPS-E3
User Guide
Table C — 48V–3.0kW 600A systems
Electrical
System Capacity (max)
Systems with LVBD
Systems without LVBD
Amperage
625A total
550A load
550A battery
625A total
Input
Operating voltage
208 to 277Vac (nominal)
Extended (high)
277 to 310Vac
Extended (low)
90 to 187Vac (de-rated O/P power)
Recommended AC
breakers
23" system: Up to 4× 40A feeds & 2× 20A Ffeeds
Efficiency
>96% peak efficiency
Output
Current per module
(nominal input)
62.5A at 48Vdc
55.5A at 54Vdc
Rectifier positions
23" system: up to 10 rectifiers
Mechanical
23" system
Mounting
Flush/center
Dimensions (H × W × D)
10.1" × 23" × 19.5"
Hot positions
26× load breakers 26x sets of ¼" studs on 5/8" centers
Return positions
26× sets of 1/4" studs on 5/8" centers
Weight (system)
27.2kg (60lbs)
Weight (rectifier)
1.76kg (3.88lbs) per module
System access
Front access after initial installation
Controller
Cordex HP
Environmental
Temperature
-40 to 55°C (-40 to 131°F)
55 to 65°C (-40 to 149°F) de-rated output
Humidity
0 to 95% RH non-condensing
Elevation
-500 to 2000m (-1640 to 6600ft)
Compliance
Safety
CSA C22.2 No. 60950-1-07
UL 60950-1