15
9400016-J0 Rev E
CXPS-E3
User Guide
4.2.2 400A 23inch power center
Provides up to 26 breakers which can be configured as all load breakers (26 load breakers) or a mix of load and
battery breakers (21 load breakers and 5 battery breakers).
The all load breaker configuration has a shunt that monitors the total load current supplied by the rectifiers to the
load.
The load and battery configuration has a shunt that monitors the total battery charge and discharge current and
includes a low voltage battery disconnect (LVBD).
Both the hot and return connections are made on ¼" studs on 5/8" centers using narrow tongue lugs. Adapter
kits for landing larger cables are available when higher capacity 2 or 3 pole breakers are required.
4.2.3 600A 23inch power center
Provides up to 26 load breakers with configurable battery landing outputs. The all load breaker configuration
has a shunt that monitors the total load current supplied by the rectifiers to the load. The low voltage battery
disconnect configuration has a shunt that monitors the total battery charge and discharge current and includes a
low voltage battery disconnect (LVBD).
Both the hot and return connections are made on ¼" studs on 5/8" centers using narrow tongue lugs. Adapter kits
for landing larger cables are available when higher capacity 2 or 3 pole breakers are required.
4.2.4 Control and monitoring methods
The CXPS-E3 front panel provides inputs and outputs for load and battery voltage, battery or load current,
breaker alarms and disconnect control as well as monitoring. Additional IO (expansion) is available for customer
use. See the following table for the details.
Table D — Control and monitoring methods
Features
L-ADIO
Dedicated IO:
Bus voltage monitoring (2)
Breaker alarm monitoring (2)
Dry contact– breaker alarm (2)
Bus voltage sense (2)
Expansion IO
(customer use):
Temperature sensor inputs (4)
Form C relay outputs (12)
Digital inputs (6)
Voltage sense Inputs (2)
Current shunt Inputs (4)
Cordex HP controller
Local connection to L-ADIO
Advanced UI
Ethernet connection
4.2.5 Breaker labelling
For systems with load only outputs, the numbering goes from left (1) to right ( 21 for a 19" or 26 for a 23")
For systems with batteries and loads the load numbering goes from left (1) to center/right (16 for a 19" or 21 for a
23") and the battery labelling goes from right (1) to left (5).
There is a label on top of the front door which can be seen from the top when the door is closed, and from the
front when the door is open. This label is larger and suitable for writing information about the breaker position.
There are two additional labels for breaker identification: a thin label above the breaker which can be read from
the front (not writable), and one on the back/top near the return breakers which identify the positions of the return
(not writable).