SCALE:
REV
SHEET
SIZE
DWG NO.
TITLE:
OF
F
N.T.S.
B
1
2
030-716-08
CUSTOMER CONNECTION, 23" SHELF, 3.6KW CORDEX
THESE DESIGNS AND SPECIFICATIONS ARE
CONFIDENTIAL, REMAIN THE PROPERTY OF
ALPHA TECHNOLOGIES LTD., AND SHALL NOT BE
COPIED OR USED WITHOUT ITS WRITTEN CONSENT
© ALPHA TECHNOLOGIES LTD
CHECKED
DRAWN
DATE
APPROVALS
JK
Feb/01/05
Mar/01/05
JU
X.X X.XX X.XXX ANGULAR:
THIRD ANGLE PROJECTION
UNLESS OTHERWISE SPECIFIED
DIM ARE IN INCHES
INTERPRET DIM AND TOL PER
ASME Y14.5M -1994
0.040
1
0.020 0.010
AC WIREWAY, BOTH SIDES,
1.3 HOLE FOR CUSTOMER
SUPPLIED 1" CONDUIT FITTING
PROTECTIVE EARTH TERMINAL 2 PLACES
AC WIREWAY BLANK PLATE
SEE DETAIL 'A'
DETAIL 'A' - AC INPUT OPTIONS
REAR - AC REAR COVER REMOVED
SWITCH SETTING FOR CAN TERMINATION
CAN TERMINATED
CAN UNTERMINATED
J8
J7
CAN OUT RJ12 OFFSET
PIN OUT (J8)
CAN IN RJ12 OFFSET
PIN OUT (J7)
GND
1.
CAN H
2.
NOT CONNECTED
3.
CAN L
4.
NOT CONNECTED
5.
NOT CONNECTED
6.
GND
1.
CAN H
2.
NOT CONNECTED
3.
CAN L
4.
NOT CONNECTED
5.
NOT CONNECTED
6.
L3
L2
L1
L2
L3
N
N
L2
L3
N
N
CONNECT NEUTRAL TO ANY ONE OF THE THREE TERMINAL BLOCK POSITIONS LABELED 'N'
L1
L2/N
L2/N
L1
L2/N
L1
DO NOT CONNECT AC TO THIS INPUT WHEN CXCM4 IS USED IN THE SHELF
LIST 83: DUAL 3-PHASE INPUTS, 208-240VAC
NO NEUTRAL
LIST 84: DUAL 3-PHASE INPUTS, 360-480VAC
WYE SOURCE, NEUTRAL REQUIRED
LIST 85: SINGLE PHASE INPUTS, 208V-277VAC
L1
L3
L2
L1
L2/N
L1
L2/N
L2/N
L1
F
L1
N
N
L1
REVISIONS
LTR
DESCRIPTION
DWN
DATE
CHK
B
LIST 81 UPDATED
MP/JU
Oct/01/05
WES
C
CORRECTED VIEW DESCRIPTIONS
MP
Oct/15/05
GS
D
UPDATED LIST 85 LABELS
SDW
Mar/01/08
GIA
E
REVISED FOR SOLIDWORKS INTEGRATION
JL
Oct/01/10
SY
F
ADDED NOTE TO DETAIL A
JMAR
Aug/25/14
SP
A
B
C
D
E
1
2
3
4
5
D
A
C
E
B
1
3
5
4
2
DO NOT SCALE DRAWING