12
016-564-B0-001, Rev. A1 (05/2022)
2.0 Installing an Alpha
®
APX3-G Unit
2.1 Enclosure Grounding
Fig. 2-1, Grounding Enclosure
Service Drop
To Service Entrance
Meter
Copper Ground Rod
12.7mm × 2.4m (1/2" × 8')
Service Entrance
Mounting Bracket
APX3-G
#8 AWG (Minimum)
Copper Ground Wire
Output Coaxial Cable
Utility Power Input
(From Service Entrance)
Alpha
®
recommends using the grounding method illustrated below. The grounding method may vary depending on
local codes and other site-specific characteristics.
NOTICE
: