6021642 DIAM4200 2.5 to 20KVA rev 1-9.docx
II-28
II
INSTALLATION
II.1
PREPARATION
II.1.1 EQUIPMENT RECEPTION
II.1.1.1 Equipment delivered:
The following are delivered with the CCR:
The “Installation and Maintenance” instructions manual for the device
A leaflet detailing possible added (non regular) options
Factory test report for the device
II.1.1.2 Checking the equipment:
When the device is received, check that the frame and its components (in particular the electronic and
LV units) are in good mechanical condition with no distortion or signs of impact.
Check also that the power transformer shows no signs of being transported in a wrong position and that
its protective packaging is not damaged.
II.1.2 DEVICE LOCATION
In deciding the permanent operating location for the device, the following points must be kept in mind:
An easy access must be kept to the front panel with no obstruction preventing the panel being opened.
CCRs can be placed side-by-side
Leave a gap of at least 20cm at the back of the device to allow sufficient ventilation
Environmental conditions must be such that the temperature does not go outside the range -40°C to
+55°C and that relative humidity does not exceed a maximum of 95%.
The location must be compatible with the “IP21” protection index of the CCR.
Summary of Contents for OCEM AUGIER DIAM4200 Series
Page 50: ...6021642 DIAM4200 2 5 to 20KVA rev 1 9 docx V 50 ...
Page 51: ...DIAM4200 2018 AUGIER SA 6021642 DIAM4200 2 5 to 20KVA rev 1 9 docx V 51 ...
Page 52: ...6021642 DIAM4200 2 5 to 20KVA rev 1 9 docx V 52 ...
Page 53: ...DIAM4200 2018 AUGIER SA 6021642 DIAM4200 2 5 to 20KVA rev 1 9 docx V 53 ...
Page 54: ......
Page 55: ...DIAM4200 2018 AUGIER SA 6021642 DIAM4200 2 5 to 20KVA rev 1 9 docx V 55 ...