DIAM4200 ©2018 AUGIER SA.
6021642 DIAM4200 2.5 to 20KVA rev 1-9.docx
I-23
I.7
ACCESSORIES
I.7.1
“ALIZE4100” SOFTWARE
The CCR is configured in factory but its parameters can be changed directly on the equipment without
using any special accessories. The CCR can also be configured via a PC-type computer linked to the USB
socket on the front of the device.
The free software, called “ALIZE4100”, allows to :
Configure the device and save or retrieve the parameters in a file.
Download the CCR’s software at
http://www.augier.com/soft/ALIZE4100.exe
Help maintenance people in fault diagnosis (Displaying internal voltages, state of inputs/outputs,
etc).
Test and monitor the CCR, allowing to send remote orders and to see its back indication.
I.8
OPTIONS
I.8.1 CUT OUT (OPTION)
AUGIER/OCEM
’s experience regarding CCRs has been used to simplify the HV compartment and
maintenance operations to the maximum.
With that option, the CCR is equipped with an cut-out which allows to carry out all maintenance and
measurement operations, without unscrewing any load terminal or earth connection, and without requiring any
special tools.
SEE NOTICE 6021752
.
I.8.2 EARTH FAULT DETECTOR (EFD)
This option is used to measure the insulation of the load with respect to earth.
The insulation controller, or “earth fault detector” continually checks the electrical resistance between
the loop and earth. It uses the principle of continuous current injection at 500V and its range of measurement is
between 1 k
and 50 M
.
The insulation resistance value can be seen in the “
Monitoring
” menu
Two comparison levels (warning and alarm) are available. They are preferably set at 1M
and 100k
.
Setting the
Level EFD1 and Level EFD2
parameters:
Go into the menu “
Alarms and Warnings”
then “
Earth fault
”.
Remote indication :
Each level passed is indicated by a contact relay
The insulation resistance value, levels and warnings are transferred to the Jbus table.
Note: this option can be used to diagnose lightning arrestor status. This possibility is fully explained
during the CCR training course.
Summary of Contents for OCEM AUGIER DIAM4200 Series
Page 50: ...6021642 DIAM4200 2 5 to 20KVA rev 1 9 docx V 50 ...
Page 51: ...DIAM4200 2018 AUGIER SA 6021642 DIAM4200 2 5 to 20KVA rev 1 9 docx V 51 ...
Page 52: ...6021642 DIAM4200 2 5 to 20KVA rev 1 9 docx V 52 ...
Page 53: ...DIAM4200 2018 AUGIER SA 6021642 DIAM4200 2 5 to 20KVA rev 1 9 docx V 53 ...
Page 54: ......
Page 55: ...DIAM4200 2018 AUGIER SA 6021642 DIAM4200 2 5 to 20KVA rev 1 9 docx V 55 ...