Figure 5. Wiring the Control Cable
17
7.0 Wiring the Control
Cable to Control/
Display Unit
7.1
Remove cover from C/D unit by pulling the cover outward
first on one side and then the other. Be extremely careful
not to damage the hinge posts which protrude out approxi-
mately 1/2" on each side of the lower front of the unit.
7.2
Pass the four wires of the control cable through the
square hole in the rear of the enclosure and through the
3/8" diameter hole in the printed circuit board (PCB).
Strip approximately 1/2" off of each wire end.
7.3
The control cable consists of four #18 AWG Conduc-
tors. These are typically black, white, green and red.
To insure proper operation and noise immunity, do not
run these wires parallel to or next to high voltage (Class
I) circuits. Connect the wires as shown in Table 1 and
in Figure 5.
9212 CONNECTIONS
CDC3
CDC4
CD2
CD1
GREEN
RED
BLACK
WHITE
OUT 2
OUT 3
CLASS 2
RELAY
OUTPUTS
9202
DATA/LINK
BOARD
CT1
CTC
CTC
CT2
1
2
3
4
5
CLASS 2
OUTPUTS
CT2
CT1
WHT
BLK
BLK
WHT
A/C #2
A/C #1
8
7
6
CD1-
R
E
D
CDC-
G
R
N
CDC-
B
LK
CD2-
W
HT
DISPLAY
UNIT
RELAY UNIT
CONTROL/
OR2
No Connect
9841A