Venting System
Energy King’s factory built fireplace is designed to operate on a variety of 6" HT tested chimneys. Figure
14 shows a typical installation. When installing the HT chimney, follow the chimney manufacturer’s
installation instructions. All chimney sections must be secured. The anchor plate, which is supplied by the
chimney manufacturer, must be sealed and fastened to the unit top with 4 screws and sealed with high
temperature silicone sealer.
The chimney must be a minimum of 12' overall height with a minimum of 3' above the roofline and 2'
above any obstructions within 10' (see Figure 14 below). The minimum draft of the fireplace is .06" of
water column.
A straight chimney is best. Up to two 30-degree elbows can be used for offsets.
Figure 14
All chimney installations must be installed in
accordance with chimney manufacturer’s
requirements.
Chimney
Use only listed type HT chimney for this fireplace. Do not vent any other appliances through this chimney
system. Follow the chimney manufacturer’s instructions for proper installation of the chimney. Be sure the
chimney system has an anchor plate available for the fireplace. See Figure 14 above for chimney height
requirements. In case of chimney offsets or marginal draft, use an 8" High Temperature Listed Chimney.