7  SYSTEM MENU 

Every time it becomes necessary to change or set new parameters on the equipment, the user must 

access the Menu. 

To access the menu, the key 

MENU

 must be pressed for 3 seconds. 

After access use the keys 

COMP

▲ 

and 

E-HEATER

 ,to navigate the menus and submenus. 

In order to confirm values/parameters press the key 

OK/LOCK

. Press the key 

CANCEL

 to exit the 

menu. 

8  ERRORS 

Symbols 

Description 

Problem / Checking 

Er01 – S1 

Anomaly 

detected in probe 

Damaged probe - Measure the probe's internal resistance 

which at a temperature of 25ºC is approximately 10 KΩ.

 

Probe disconnected from the controller - Check that the 

connector is securely connected to the electronic board 

and/or that the connection terminals are tight. 

Er02 – S2 

Anomaly 

detected 

in probe 2, 

when applicable 

E03 – TA 

Anomaly 

detected in water 

temperature 

Water temperature in storage water heater is too hot – 

Check that there is no anomaly in the electronic board, such 

as a damaged relay. 

Temperature probes in short-circuit – Measure internal 

resistance of probe, it should be approximately 10 KΩ at the 

temperature of 25ºC, check that the connector is well 

attached to the electronic plate and the connection 

terminals are in good condition. 

Error “Lo” 

Temperature 

probe is 

damaged or in 

short-circuit 

Check the connections of the temperature probe. 

Replace with new probe. 

LP 

Protection 

system is 

activated 

Check low pressure switch – Check if the connector is well 

attached to the electronic plate and that the connection 

terminals are secure, or that the pressure gauge is running. 

Lack of refrigerant fluid in the circuit – Load of refrigerant 

incomplete or leak. Low external temperature. 

LINK 

ERROR 

Communication 

failure 

Connection cable between display and command panel 

– Check the cable is in good condition or that the plugs are 

correctly inserted (display and command panel). 

 
 

 

Summary of Contents for ECO 200i

Page 1: ...250ix 300esm 300i 300ix 200is 250is 250isx 300esms 300is 300isx 500is 500isx TECHNICAL MANUAL EN European Certification EN 60335 1 EN 60335 2 21 EN 60335 2 40 Directives 2006 95 CE Revision 16 Versio...

Page 2: ......

Page 3: ...vations that will promote power saving in our products Your choice has demonstrated your good sense and concern with power consumption a matter that affects the environment We have taken on a permanen...

Page 4: ...st Corrosion if applicable 19 3 5 5 Dielectric Joint enamelled boilers 19 3 5 6 Expansion Vessel 20 3 5 7 Safety Group 20 3 5 8 Pressure Reducing Valve 20 4 INSTALLATION 21 4 1 Attachment of the Panel...

Page 5: ...rating Mode 37 6 5 Extra Modes 37 6 5 1 DISINFECT Function 37 6 5 2 VACATION Mode 38 6 5 3 PV Mode 38 7 SYSTEM MENU 39 8 ERRORS 39 9 PARAMETERS DESCRIPTION 40 10 PROBE CHART 41 11 TROUBLESHOOTING 41 1...

Page 6: ...f the power supply cable is damaged it must be replaced by the manufacturer by its customer service or by staff with similar training in order to avoid any danger ECO will only operate if the storage...

Page 7: ...ualified person WARNING DANGER In order to avoid any danger due to the untimely rearming of the thermal circuit breaker the device must not be powered by an external switch such as a timer or connecte...

Page 8: ...ion of material Refrigerant The refrigerant used in the entire process is R134a CFC free non inflammable and without harmful effects to the ozone layer However according to the law the fluid in this e...

Page 9: ...h fixing elements and the other with the thermo accumulator and the attached thermodynamic group The packages contain 1 Thermodynamic solar panel with fastening elements 2 Storage water heater 3 Therm...

Page 10: ...ng the water heater and the thermodynamic block must be transported in an upright position and in the correct direction Horizontal transport or with the equipment turned upside down can cause serious...

Page 11: ...the R134a ecological refrigerant evaporates inside the solar panel The absence of glass on the panel allows to increase the thermal exchanges by convection After passing through the panel the R134a is...

Page 12: ...Monophase 50 ou 60 Fuse Main Electrical Heater A 10 10 Working Temperature C 5 45 PERFORMANCE Tapping Porfile L XL XL XL XL Coefficient of Performance COP Air 2 C 2 8 2 9 2 9 2 9 2 9 Air 7 C 3 1 3 2...

Page 13: ...ou 60 Fuse Main Electrical Heater A 10 10 Working Temperature C 5 45 PERFORMANCE Tapping Porfile L XL XL XL XL XXL XXL Coefficient of Performance COP Air 2 C 2 76 2 8 2 8 2 8 2 8 2 9 2 9 Air 7 C 3 09...

Page 14: ...appliance The safety device must be in compliance with the standard EN 1487 2002 maximum pressure 7 bar 0 7 MPa Water must not be stopped from flowing from the safety device to the deposit by any sor...

Page 15: ...107 102 Cold Water C G 1 M 231 236 635 Coil Outlet D 435 436 Instrumentation E G 1 M 690 636 1525 Coil Inlet F G F 840 840 782 855 782 Recirculation G G 1 M 1025 1096 1093 Magnesium Anode H G F 905 13...

Page 16: ...D Plate Any contact with the installer or manufacturer must be accompanied by Model Serial number Date of production The provision of these data will facilitate all communication and consequently a fa...

Page 17: ...he connection side Left Panel Right Panel The panels have the following pipe diameters 3 8 aspiration upper joint 1 4 liquid lower joint In the case of panel equipment the refrigerant connections are...

Page 18: ...onnected to the condenser which surrounds the water heater through two One Shot valves Storage Water Heater The domestic hot water storage heater is vertical resting on the ground Thermal insulation i...

Page 19: ...s this value the thermostat switches off the backup electrical heater Switching on is done manually by qualified staff after analysing the reasons for the switch off 3 5 3 Temperature Probe The purpos...

Page 20: ...e The pressure reducing valve must always be installed upstream from the safety device and ready to activate in situations when the pressure in the circuit exceeds 3 bar 0 3MPa This valve comes with a...

Page 21: ...unlight exposure the panels Should have a pitch between 10 and 85 relative to the horizontal plane and preferably oriented to the south The panel already comes with 6 holes for M8 in the lateral skirt...

Page 22: ...lope of 45 The profile must be fixed to the base eg tile using a plastic anchor and M6 screw provided The panel is fixed to the profiles using the M6 screws and the respective nuts and washers The pan...

Page 23: ...respect this parameter can lead to the exclusion of the warranty Make sure that the support surface is sufficient to accommodate the weight of the water filled water heater Provide at least 500mm of...

Page 24: ...purpose Refrigerant connections must be thermally insulated to prevent burns and to ensure optimum system performance The system has an R134a fluid preload 4 4 1 Connections to the panel 1 Thermodyna...

Page 25: ...2 Thermodynamic Panels a Prepare the copper pipe removing the protective caps from the extremities b Place the extremity of the pipe upside down cut the appropriate size of pipe and sand the rough ed...

Page 26: ...ctions Exit of the panels the same symmetry accuracy in the length of the tubes is not required The same should be done by chipping or with a T as shown in the following image properly isolated The ty...

Page 27: ...of the pipe employed according to table in point 4 4 1 Insufficient torque will cause leaks of refrigerant Excessive torque on the coupling will damage the edge of the pipe and cause leaks 4 4 3 Conne...

Page 28: ...eed to the following points The water heater thermodynamic group is filled with fluid The closed valves ensure that the fluid does not escape during the next steps All connections must be isolated 1 3...

Page 29: ...ate a vacuum with the vacuum pump plugged to the inlet of the 3 way pressure valve as depicted keeping the valves completely shut The vacuum should be at least 30min for installation of one panel and...

Page 30: ...t a complementary load of gas follow these steps a Place the cooling fluid tank on a scale with a 10 g precision and take note of the weight b Connect the hose of the cooling fluid tank R134a to the i...

Page 31: ...mm from the pavement to allow visual inspection WARNING We recommend the installation of a shut off section valve between the gate valve and the coupling to the storage water heater for the purpose of...

Page 32: ...cal Manual 32 ECO 4 6 1 Wiring diagram 1 Thermodynamic Panel S1 Temperature probe Comp Compressor LP Low pressure switch R1 Support electrical heater D1 Circuit breaker TB Safety thermostat Q1 Differe...

Page 33: ...anual 33 ECO 4 6 1 Wiring diagram 2 Thermodynamic Panels S1 Temperature probe Comp Compressor LP Low pressure switch R1 Support electrical heater D1 Circuit breaker RL Relay Q1 Differential TB Safety...

Page 34: ...hether the installation is set up according to the recommendations and that everything is in conformity then you may plug your equipment to the power supply After switching on your equipment you shoul...

Page 35: ...itch on off Switch on and off controller CANCEL Exit ESC function to exit menu submenu or cancel a function OK OK Confirmation Confirm parameters within menus or submenus LOCK Lock Unlock Lock or unlo...

Page 36: ...o Mode LP Electrical heater is activated by opening of LP contact Auto Boost Mode M Electrical heater is manually activated 6 4 Operating Modes ECO is programmed to work in 3 running modes ECO AUTO an...

Page 37: ...N OFF 6 4 3 BOOST Operating Mode In BOOST operating mode the equipment runs as a Heat Pump Electrical Heater and the running of the electrical heater is simultaneous with the Heat Pump This mode enabl...

Page 38: ...on offers the possibility to raise the water temperature when an alternative electrical energy source is available solar photovoltaic wind or other increasing the efficiency of the heat pump and makin...

Page 39: ...emperature Water temperature in storage water heater is too hot Check that there is no anomaly in the electronic board such as a damaged relay Temperature probes in short circuit Measure internal resi...

Page 40: ...ctivate electrical heater 1 40 Value 16 C Parameter ON T01 Delay time to compressor starts running 1 20 2 min T05 Maximum time compressor running AUTO 6h 15h Value 12 horas Parameter ON T07 Delay time...

Page 41: ...function Check the presence of error on electronic board and consult the table of errors Use of large amount of hot water Set BOOST mode and wait for water heating Low temperature programmed in the Se...

Page 42: ...g of expansion tank Pressure in circuit is high if the leak is continuous Check the throttle valve if there is one installed Installation of a throttle valve if it lacks one Consumption abnormally hig...

Page 43: ...pressure for example open a hot water tap Unscrew the anode with a suitable tool Check the level of wear of the anode and replace it if necessary If the diameter of the anode is less than 15mm it will...

Page 44: ...a separate collection centre for electrical electronic equipment or returned to the retailer at the time of purchasing new equipment The end user is responsible for delivering the end of life device...

Page 45: ......

Page 46: ......

Page 47: ...n any form of intervention by unauthorized technicians has the appearance of modifications and or if the series number appears to have been removed or erased The equipment should be installed by quali...

Page 48: ......

Page 49: ...NOTES...

Page 50: ......

Page 51: ......

Page 52: ......

Reviews: