Maintenance
Maintenance plan
24
Maintenance
Maintenance plan
The maintenance work specified in this summary must be
carried out after the indicated time intervals.
Time interval in operating hours [h]
Maintenance work
before
each start
every 50 hours
or 3 months
every 100
hours or 6
months
every 300
hours or
every year
check
X
Motor oil
(see p. 25)
change
X
check
X
Air filter
(see p. 26)
clean / replace
X
(1)
Spark plugs
(see p.28)
clean / check gap
X
Valves
test / adjust
X
(3)
Check fit of screws and bolts
X
(2)
X
Fuel lines check / replace
X
(3)
Earth connections check
every 2 years
(3)
1) In dusty environments, every 10 hours
2) After first operation
3) Only by an authorized professional workshop
ATTENTION!
Before the generator is maintained or cleaned, it must
cool off.
Generally, the generator must be cleaned at regular inter-
vals, depending on the operating environment.