Commissioning
Hauser
21
6.4
Testing the internal switch
When the housing cover is open, the function of the internal switch to switch off the motor can
be checked by inserting a screwdriver into the opening provided in the electronics cover and by
moving the handle to the side.
T
est
D
en
sity
h
ig
h
lo
w
A0017369
å
16
Testing the internal switch
7
Commissioning
7.1
Post-installation and post-connection check
Checklists:
• Post-installation check(
7.2
Setting the switching pressure
The switching pressure of the point level switch can be adapted to the bulk solids
(
• Slight:80 g/l (4.99 lb/ft³)
• Medium (factory setting):100 g/l (6.24 lb/ft³)
• High:120 g/l (7.49 lb/ft³)
7.3
Switching on the device
The shaft starts to turn as soon as the supply voltage is switched on. The rotational movement
can be observed from the outside.