Troubleshooting

Functional testing of the point level switch by testing the internal switch (

®

  

å

 16, 

ä

 21)

8.1 

Point level switch with rotation monitoring

The table below shows the output signal of the point level switch with rotation monitoring for
overfill protection.

Rotation monitoring of the FTE20 (optional)

Power supply

Motor

Output signal of "full" sensor

On

Shaft turns

-

On

Shaft does not turn, rotating paddle is
covered

Full

On

Shaft does not turn, rotating paddle is
not covered

Full

Off

Full

If the rotation monitoring system detects an error, a "full" alarm is signaled and the light in the
electronics housing flashes.

Function testing of the point level switch

Operate the internal switch

1. Insert a screwdriver or another suitable tool in the opening provided in the electronics

cover and move it in the direction indicated, see Testing the internal switch
(

®

  

å

 16, 

ä

 21).

Ã

The switch is operated and the empty/full alarm is reset.

Summary of Contents for Soliswitch FTE20

Page 1: ...Operating Instructions Soliswitch FTE20 Point level switch BA01069F 09 EN 01 12 71186553...

Page 2: ......

Page 3: ...eptance transport storage 9 4 2 Installation conditions 9 4 3 Installation instructions 11 4 4 Post installation check 15 5 Wiring 16 5 1 Connection instructions 16 5 2 Quick wiring guide 16 5 3 Post...

Page 4: ...symbol alerts you to a dangerous situation Failure to avoid this situation can result in minor or medium injury NOTICE A0011192 EN NOTICE This symbol contains information on procedures and other fact...

Page 5: ...additional information A0011194 Reference to documentation Refers to the corresponding device documentation A0011195 Reference to page Refers to the corresponding page number A0011196 Reference to gr...

Page 6: ...the Operating Instructions and supplementary documentation as well as in the certificates depending on the application Following instructions and basic conditions The operating personnel must fulfill...

Page 7: ...ertaining to repair of an electrical device Use original spare parts and accessories from Endress Hauser only Hazardous area To eliminate a danger for persons or for the facility when the device is us...

Page 8: ...and manufacturer s address 3 2 Certificates and approvals An overview of all the approvals available is provided in the Technical data section CE mark Declaration of Conformity The device is designed...

Page 9: ...or the content damaged Is the delivery complete Compare the scope of delivery against the information on your order form 4 1 2 Transport and storage Please note the following Pack the device so that...

Page 10: ...ss Hauser 1 3 2 4 200 7 87 mm in 5 A0017073 2 Correct installation positions of the point level switch 1 Vertical from the top 2 Angled from the top 3 From the side 4 From the side with protective cov...

Page 11: ...Ambient temperature range 20 to 60 C 4 to 140 F Medium temperature range 20 to 80 C 4 to 176 F More information is provided in the Technical data section 23 4 3 Installation instructions NOTICE The d...

Page 12: ...allation of the standard version 1 Sealing ring 60x48x3 mm 2 36x1 89x0 12 in 2 Open ended wrench AF 60 NOTICE Function of device with hinged rotating paddle restricted by transport lock Remove the tra...

Page 13: ...on Endress Hauser 13 1 2 1 2 3 A0017363 5 Installation of the version with the hinged rotating paddle 1 Sealing ring 2 Open ended wrench AF 32 4 3 1 Turning the housing to the right position A0017364...

Page 14: ...he dimensions are provided in the Technical data section 30 A0018473 7 Installation of the flange version 4 3 3 Mounting the weather protection cover The weather protection cover is available as an ac...

Page 15: ...t the cover from opening Additional installation instructions for the hazardous area are provided in the separate Ex documentation for the device optional T10 A0017368 9 Tightening the cover securing...

Page 16: ...lose to the device within easy reach and marked as a circuit breaker An overload protection element rated current 10 A is required for the power cable If replacing an older Soliswitch FTE3x with a new...

Page 17: ...tput signal FTE20 and FTE20 with rotation monitoring Lamp not lit Shaft turns No Full signal Shaft turns Refill signal B output signal FTE20 and FTE20 with rotation monitoring Lamp lit Shaft does not...

Page 18: ...Wiring Soliswitch FTE20 18 Endress Hauser 5 2 2 Inserting the cable 1 2 A0017367 11 Remove the housing cover 3 4 5 A0017365 12 Guide the cable through the cable entries...

Page 19: ...Does the supply voltage match the specifications on the nameplate 1 8 20 to 28 V DC 24 V AC 115 V AC 230 V AC Are the mounted cables connected correctly and strain relieved Are the cable glands secure...

Page 20: ...addle The disk s viewing area is lit up by an LED to make it easier to see The rotational movement of the disk and therefore also the shaft can be checked through an inspection opening in the cover of...

Page 21: ...369 16 Testing the internal switch 7 Commissioning 7 1 Post installation and post connection check Checklists Post installation check 15 Post connection check 19 7 2 Setting the switching pressure The...

Page 22: ...nitoring of the FTE20 optional Power supply Motor Output signal of full sensor On Shaft turns On Shaft does not turn rotating paddle is covered Full On Shaft does not turn rotating paddle is not cover...

Page 23: ...length 9 1 2 Measuring range The measuring range depends on the installation location of the Soliswitch FTE20 and the selected length of the shaft 75 to 300 mm 2 95 to 11 81 in or the rope extension u...

Page 24: ...rminals with spring terminal design Permitted cable cross sections Rigid 0 2 to 2 5 mm 24 to 14 AWG Flexible 0 2 to 2 5 mm 24 to 14 AWG Flexible with wire end ferrule without plastic ferrule 0 5 to 2...

Page 25: ...on From below Cable entry must point downwards In direction of solids flow Installation socket too long Horizontal with shaft length 300 mm 11 8 in 9 5 2 Special mounting instructions Side load on the...

Page 26: ...mmunity As per IEC 61326 1 industrial environments Interference emissions As per IEC 61326 1 Class B 9 6 5 Electrical safety Protection class I overvoltage category II pollution level II 9 6 6 Operati...

Page 27: ...ons 103 4 06 113 4 45 SW AF 60 105 4 13 157 6 18 131 5 16 130 5 12 126 8 4 99 101 8 4 01 2000 78 7 108 4 25 28 8 1 13 136 8 5 39 130 5 12 L 25 0 98 L 40 1 57 L 27 5 1 08 L 52 5 2 07 mm in 1 2 A 1 A001...

Page 28: ...on NPT 1 NPT 1 G 1 B Process connection G only available with hinged rotating paddle L Length of shaft 75 to 300 mm 2 95 to 11 81 in 9 8 2 Weight Version part Weight approx FTE20 with shaft 100 mm 3 9...

Page 29: ...by a reflector disk fitted on drive shaft of the paddle and can be monitored through a sight opening in the drive terminal cover The disk s viewing area is lit up by an LED to make it easier to see I...

Page 30: ...s Hauser 9 10 1 Device specific accessories Accessories Description Flange version 150 5 91 150 5 91 18 0 71 48 1 89 2 0 08 mm in 15 0 59 15 0 59 A0018472 20 Dimensions of the flange connection Order...

Page 31: ...ive cover Used to protect the measuring device from the adverse effect of the weather when fitted in the roof of a silo 6 2 2 4 4 175 6 89 201 5 7 93 298 5 11 75 103 4 06 221 5 8 72 mm in A0017694 21...

Page 32: ...BA01069F 09 EN 01 12 71186553 EH COSIMA ProMoDo...

Reviews: