Commissioning
Prosonic M FMU44 HART
32
Hauser
9.5.3
Envelope curve display (0E3) function
If cyclic envelope curve display is active on the display, the measured value is updated
at a slower cycle time. Recommendation: exit the envelope curve display after
optimizing the measuring point. Press (the device does not leave the envelope
curve display automatically.)
Conditions
• The echo quality at the end of measuring range is at least 10 dB
• There should be practically no interference echoes in front of the actual level signal
• Interference echoes must be below the mapping curve
1
2
3
4
5
6
7
A0038455
27
Envelope curve
1
Full calibration
2
Quality of the evaluated echo
3
Marking for the evaluated echo
4
Empty calibration
5
Display end value
6
Distance of the evaluated echo
7
Display start value
1
2
3
A0038456
28
Envelope curve and mapping
1
Mapping
2
Interference echo
3
Level echo
9.5.4
Navigate in the envelope curve display
Active navigation mode: symbol in the top left-hand corner of the display
Horizontal zoom mode
• Zoom in
• Zoom out
Move mode
• Move left
• Move right
Vertical zoom mode
Zoom in or out in 4 steps 0 to 3