Prosonic M FMU44 HART
System integration
Hauser
23
7.5
Locking or enabling parameter configuration
7.5.1
Software locking
1. Navigate to:
"Diagnostics" (0A)
function group →
"Unlock parameter" (0A4)
function
2. Enter a number ≠100.
The symbol appears on the display. Additional entries are no longer possible.
3. If an attempt is made to change a parameter, the device jumps to
"Unlock
parameter" (0A4)
function.
4. Enter the number "100".
The parameters can be changed again.
7.5.2
Hardware locking
1. Press simultaneously.
Additional entries are no longer possible.
2. If you try to change a parameter, the following appears:
"Unlock parameter" (0A4)
function with the symbol.
3. Press simultaneously.
The
"Unlock parameter" (0A4)
function appears.
4. Enter the number "100".
Parameters can be changed again.
Hardware locking only possible via the display: press again simultaneously.
Hardware unlocking via communication is not possible.
8
System integration
8.1
4 to 20 mA output with HART protocol
8.1.1
Operation via Field Xpert
Compact, flexible and robust industrial handheld terminal for remote configuration and for
obtaining measured values via the HART current output or FOUNDATION Fieldbus. For
details, see the Operating Instructions BA00060S/04.
8.1.2
Operation with FieldCare
FieldCare is an Hauser asset management tool based on FDT technology.
FieldCare configures all Hauser devices and devices from other manufacturers
that support the FDT standard.
Hardware and software requirements: www.de.endress.com - Search: FieldCare
FieldCare supports the following functions:
• Configuration of transmitters in online mode
• Signal analysis with envelope curve
• Tank linearization
• Loading and saving of device data (upload/download)
• Documentation of the measuring point