Installation
2.1 Transporting to the measuring point
• Transport the measuring device to the measuring point in the original packaging.
• The covers or caps fitted on the process connections prevent mechanical damage to the
sensors during transport and storage. For this reason, do not remove the covers or caps until
immediately before installation.
2.2 Installation conditions
For mechanical reasons, and in order to protect the piping, it is advisable to support heavy
sensors.
2.2.1 Dimensions
For the dimensions of the measuring device
→
see associated Technical Information on the
CD-ROM.
2.2.2 Mounting location
The following mounting locations are recommended:
• Upstream from assemblies such as valves, T-pieces, elbows, etc.
• On the pressure side of pumps (for high system pressure)
• At the lowest point in an ascending pipe (for high system pressure)
A0007408
To transport the unit, use slings slung around the
process connections or use lugs (if available).
#
Warning!
Risk of injury! The device can slip.
The center of gravity of the measuring device may be
higher than the holding points of the slings.
Always ensure that the device cannot slip or turn
around its axis.
A0007409
Do not lift measuring devices by the transmitter
housing or the connection housing in the case of the
remote version. Do not use chains as they could
damage the housing.